Outdoor DN Code
(O.DN) Setting
Operation
Operation
O.DN [19] =
0000
Normal operation
O.DN [19] =
0001
Outdoor Fan High Static Pressure operation
Model
Maximum external static pressure
㧔
∗
㧕
Outdoor unit air flow
Model
Maximum external static pressure
㧔
∗
㧕
Outdoor unit air flow
MMY-MUP
(Pa)
(m
3
/min)
MMY-
MUP
(Pa)
(m
3
/min)
0801
*
80
165
1
4A
1
*
80
2
30
1001
*
80
175
1801
*
80
280
1201
*
80
195
2001
*
80
265
1401
*
80
198
2201
*
80
275
2401
*
80
275
6-6. Applied Control of Outdoor Unit
The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are available by setting relevant switches provided on the interface P.C.
board of the outdoor unit.
6-6-1. Outdoor Fan High Static Pressure Shift
Setup
Change the outdoor DN code. (O.DN [19]) into "Outdoor Fan High Static Pressure operation."
This function must be enabled with every discharge duct connected outdoor unit for both of the header and
follower units.
Specifications
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a
maximum external static pressure not greater than specified in the table below. If a discharge duct with a
resistance greater than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static
pressures of single units are shown below (Table 1). In the case of combined use of multiple outdoor units, set
all the units to the same maximum external static pressure as the one with the lowest maximum external
static pressure.
Table 1:
Maximum External Static Pressures of Single Outdoor Units
(
) Calculate duct resistance from outdoor unit air flow.
Purpose/characteristics
1601
*
80
255
- 86 -