(3) Change the connection of wiring as shown in the below.
Outdoor Unit (22, 24HP)
Model: MMY-MUP2201", MUP2401"
1. When compressor No.1 is failure : No change the connection of wiring
2. When compressor No.2 is failure : Connection of wiring is changed as shown below.
Change the connection of wiring which is connected to the
CN21, CN22 and CN103 of "Compressor P.C.board 1" and
"Compressor P.C.board 2".
• Change to CN21 of P.C.board 1 from CN21 of P.C.board 2.
• Change to CN22 of P.C.board 1 from CN22 of P.C.board 2.
• Change to CN103 of P.C.board 1 from CN103 of P.C.board 2.
Remove the connector from "Compressor P.C.board 1"
• Remove the connector of CN102
• Remove the connector of CN852
Compressor
P.C.board 1
Compressor
P.C.board 2
CN102
CN103
CN21
CN22
CN852
(4) Turn on the power supply to all the units connected to the system.
This is the end of compressor backup operation setting.