Outdoor Unit Function Code No. (O. DN) Table (Includes Functions Needed to Perform Applied Control on Site)
DN
Item
Description
At shipment
003
Type Setting
Code range : 0000 to 0255
* DN Code [003] = 0000 : Undefined
Type
setting
DN Code
[03]
According to type
004
7-segment Display Contents
Control
0000 : Outdoor unit No.
0001 : Start priority number
0000 : Outdoor
unit No.
012
Optional Output Setting Control 1
(CN514)
0000 : Compressor Operation Output
0001 : Operating Rate Output
0000 :
Compressor
Operation Output
018
Priority Operation Mode Setting
0000 : Priority heating
0002 : Priority operation unit No.
0001 : Priority cooling
0004 : Priority indoor unit
0000 : Priority
heating
019
Outdoor Fan High Static
Pressure Shift
0000 : Usual
0001 : High Static Pressure Operation
0000 : Usual
01A
Operation standby
Heating standby
0000 : None
0001 : Stanby
0000 : None
005
Prohibition/Permission of the NFC
Setting
0000 : Allow Wave Tool Advance test operation within 48 hours elapsed from the
outdoor unit power on time.
0001 : Regardless of the elapsed time, WTA cannot start test operation.
0002 : Regardless of the elapsed time, WTA can start test operation.
0000 : Allow
WTA test
operation
007
Operation Mode Selection Control
0000 : Non-selected Indoor units keep stand-by state (thermostat OFF).
0001 : Changing non-selected indoor units the mode selected
0000 : Non-
Priority
008
0000 : 0h
0001 to 0063
(1000 h to 63000 h)
Compressor Maintenance Period
Time
0000 : 0h
0000 : Capacity demand
0001 : Power demand
009
Capacity / Power Demand Control
0000 : Capacity
demand
Code range
[0A] [0C] : 0000 to 0255 (1 kW to 255 kW)
[0B] [0D] : 0000 to 0099 (0.00 kW to 0.99 kW)
00A
Power consumption upper limit
standard value setting
Heating (For power demand)_High
0000 : 0kW
Setting Value during Demand Control for demand standard specifications can be set
with DN code [00E]. Its value for expansion specifications can be set in two steps
(DN codes [00F], [010]) during the normal operation and demand control (setting
value DN Code [00E]).
00E
Setting Value during Demand
Control
0015 : 0%
(Forcedly stop)
00F
Setting value during Demand
Control (Expansion 1)
0008 : 60%
010
Setting Value during Demand
Control (Expansion 2)
0004 : 80%
00b
Power consumption upper limit
standard value setting
Heating (For power demand)_Low
0000 : 0kW
00C
Power consumption upper limit
standard value setting
Cooling (For power demand)_High
0000 : 0kW
00d
Power consumption upper limit
standard value setting
Cooling (For power demand)_Low
0000 : 0kW
0
1
2
–
–
–
0000
0001
0002
–
–
–
Power consumption upper
limit standard value
DN Code
Heating
Cooling
No power demand function
0.01 kW
0.02 kW
–
–
10.00 kW
–
–
30.50 kW
–
–
[00A]
[00C]
0000
0000
0000
–
–
0010
–
–
0030
–
–
[00B]
[00D]
0000
0001
0002
–
–
0000
–
–
0050
–
–
Demand control
100%
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
–
0%
[010]
0
1
2
3
4 (Factory default)
5
6
7
8
9
10
11 to 14
15
DN Code
[00F]
0
1
2
3
4
5
6
7
8 (Factory default)
9
10
11 to 14
15
[00E]
0
1
2
3
4
5
6
7
8
9
10
11 to 14
15 (Factory default)