Ye
s
No
Ye
s
No
[P29]
[P31]
Compressor position detective
circuit trouble
1.
Wire/connector connection trouble
2. Compressor
trouble
3. Compressor
P
.C.
board
trouble
Other indoor trouble
(Group follower unit trouble)
Another indoor unit in the group is abnormal.
Sub-code:
1
∗
: Compressor 1, 2
∗
: Compressor 2
Are connector
connection and wiring
normal?
Check the following item.
Is the unit earth fault?
Is there earth trouble?
(Winding resistance
0.1 to
0.4
Ω?)
Is winding opened?
Check and correct circuit and
cables such as wiring to
compressor
, etc.
Replace compressor
Check compressor
P
.C.
board.
Failure
Replace
When the header unit of the group detected trouble [E03], [L03], [L07] or [L08], the follower unit of the group displays
[P31] trouble and stops.
There are no check code display and alarm record of the main remote controller
.
Cause
Check code
Check code name
Cause
Check code
Check code name
- 225 -