No.
16
Item
Display of
Operation
[[
standby]
[ Heating
standby]
Outline of specifications
<Operation standby>
Displayed on the remote controller
1) When the following check codes are indicated
• Open phase of power supply wiring [P05] was detected.
• There is an indoor unit that detected the indoor overflow
[P10].
• There is an indoor unit that detected the interlock alarm
[L30].
2) During forced thermostat OFF
• [COOL/DRY] operation is unavailable because the other
indoor unit operates with [HEAT] mode.
• [HEAT] operation is unavailable because COOL priority
(SW11-bit1 of the Outdoor I/F P. C. board is ON) is set and
the other indoor unit operates with [COOL/DRY] mode.
3) The above indoor units that cannot operate stay in
thermostat OFF status.
4) The indoor fan stops because the system performs
[Recovery operation for heating refrigerant (Oil)].
<Heating standby>
Displayed on the remote controller
The indoor fan stops in order to prevent discharge of cool air
when heating operation started or during heating operation.
(including the defrost operation during thermostat OFF)
1) Selection of the contents that can be operated by the
remote controller at the indoor unit side is possible
according to setting at the central controller side.
2) Setting contents
Remarks
•
< Operation
standby>
display
No display for wireless
type remote controller
•
< Heating standby>
display
(
: Operation possible
: Operation impossible)
Selection of
central control
mode
17
Operation from
TCC-LINK
central control
Individual
[Central 1]
[Central 2]
[Central 3]
[Central 4]
Operation on remote controller
ON/OFF
Operation
Timer
Temp.
Air speed
Air direction
setting
selection
setting
setting
setting
setting
Display of filter
sign [
]
(Not provided to
the wireless
type)
1) The filter sign is displayed with LC by sending the filter-
reset signal to the remote controller when the specified
time (150H/2500H) elapsed as a result of integration of the
operation time of the indoor fan.
2) The integrated timer is cleared when the filter-reset signal is
received from the remote controller.
In this time, if the specified time elapsed, the counted time is
reset and the liquid crystal display is deleted.
[
The filter sign is not
displayed in
RBC-ASCU11
*
.
FILTER] goes on.
15
Filter service life
2500H
150H
Type
4-way cassette type
Compact 4-way cassette type
1-
way cassette type (SH, YH)
2-
way cassette type
Floor standing type
Floor standing concealed type
Floor standing cabinet type
- 62 -