6-6-3-8. Compressor Operation Output
Locally procured
Outdoor unit
Optional PCB
(See “NOTE”)
TB1
C2
L1
PS
1
CTR1
K1
OUTPUT1
2
L2
PS
3
CTR2
CN514
PJ20
K2
OUTPUT2
4
5
6
Outdoor unit
interface PCB
Shield
wire
1
2
OUTPUT2
OUTPUT1
C2
CN514
CTR1
CTR2
K1, K2
L1, L2
OUTPUT1
OUTPUT2
PJ20
PS
TB1
Connector cable 2 ( 2 )
Connector on interface side (green)
Elapsed operation counter 1
Elapsed operation counter 2
Relays
Operation indication LEDs
Compressor 1 operation output terminal
Compressor 2 operation output terminal
Connector on optional P.C.board side
Power supply unit
Terminal block
Operation
When a compressor is in operation, a relay connected to the output terminal assigned to it is turned on (closed).
When it is at rest, the relay is turned off (open).
The output terminals are named OUTPUT1 and OUTPUT2 from left to right when facing the front of the
outdoor unit, as shown in the diagram.
Note 1
: Output Relay (K1, K2) Contact Specifications
• Output terminals (OUTPUT1, 2) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1and K2 insert a surge killer CR (for an AC power
supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
- 99 -