Chec
k code
Chec
k code name
Cause
Ye
s
Ye
s
Ye
s
No
No
Ye
s
No
[F23]
No
Connector: CN500, White
Ps sensor trouble
1. Output voltage trouble of Ps sensor
2. SV4, 4-way valve trouble
Is connection of Ps
sensor connector
correct?
Are output
voltage characteristics
of Ps sensor
normal?
Is there leakage
from SV4 valve?
Is
refrigerant bypassed from
discharge to suction of
4-way valve?
Correct connection of
connector
.
Sensor trouble
Replace
Check compressor
.
Check 4-way valve.
Replace SV4 valve.
(1) Pressure (Check joint) by pressure gauge
(2) Pressure display on 7-segment display
(3) Output voltage of I/F P
.C. board
If (1) and (2), (3) are dif
ferent, a trouble of pressure
sensor itself is considered.
If (2) and (3) are dif
ferent, check interface P
.C. board.
[F29]
(Power ON)
(Repetition)
(Approx. 3 minutes)
(Approx. 1 minute)
Ye
s
No
[F31]
Indoor other trouble
Indoor P
.C. board trouble
This trouble is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on
indoor unit P
.C.board. Replace service P
.C. board.
* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write
EEPROM data, the automatic address mode is repeated.
[SET
DA
T
A]
is displayed
on remote
controller
.
[SET
DA
T
A]
disappears.
LED (D02) 1Hz
flashes for approx.
10 seconds on
indoor unit P
.C.
board.
Reboot (Reset)
Outdoor EEPROM trouble
1.
Outdoor unit power trouble (V
oltage, noise, etc.)
2.
Outdoor I/F P
.C. board trouble
Is there any trouble
of outdoor unit
power supply?
Correct power line.
Eliminate external noise.
Replace I/F P.C. board.
[F24]
Check code
Check code name
Pd sensor trouble
Cause
Check code
Check code name
Cause
Check code
Check code name
Cause
Output voltage trouble of Pd sensor
It is output voltage trouble of Pd sensor
. Check disconnection of connection of connector (Pd sensor: CN501, red)
circuit and output voltage of sensor
.
If the sensor is normal, replace outdoor I/F P
.C. board.
- 205 -