This air conditioning (U series) has new communication specifications, and TU2C-
Link (U series) and TCC-Link (other than U series) differ in a communication type.
For the communication type and the model names such as each unit or remote
controllers, refer to the following table.
If TU2C-Link (U series) is combined with TCC-Link (other than U series), the wiring
specifications and the maximum number of connectable indoor units during group
control operation will be changed.
(1) For wiring specifications, carry out the installation, maintenance, or repair according to the attached
Installation Manual.
(2) For a communication type combination and the max. number of connectable indoor units, refer to the
following table.
• Only when all outdoor unit, indoor unit and remote control are a U series, communication method is
TU2C-LINK, and the maximum number of connectable units will be 16.
Communication type
TU2C-Link
(U series and future models)
TCC-Link
(Other than U series)
Outdoor unit
MMY-M
U
P
∗∗∗
↑
This letter indicates U series model.
Other than U series
MMY-MAP
∗∗∗
MCY-MHP
∗∗∗
Indoor unit
MM
∗
-
U
P
∗∗∗
↑
This letter indicates U series model.
Other than U series
MM
∗
-AP
∗∗∗
Wired remote controller
RBC-A
∗∗
U
∗∗∗
↑
This letter indicates U series model.
Other than U series
Remote sensor
TCB-TC
∗∗
U
∗∗∗
↑
This letter indicates U series model.
Other than U series
Wireless remote
controller kit &
receiver unit
U series outdoor unit : SMMS-u (MMY-MUP
∗∗∗
)
Other than U series outdoor unit : SMMS-i, SMMS-e etc. (MMY-MAP
∗∗∗
)
RBC-AX
U
∗∗∗
↑
This letter indicates U series model.
Other than U series
Remote
controller
wiring
L
L1
Indoor unit
Indoor unit
Remote
controller
L2
Indoor unit
For the maximum number
of connectable units, refer
to the following table.
Remote controller
inter-unit wiring
Ln
Indoor unit
The combination of unit type and the number of the maximum connection of a communication method
Unit type
Outdoor unit
U series
U series
U series
U series
*
*
*
*
Indoor unit
U series
U series
*
*
U series
U series
*
*
Remote controller
Remote sensor
U series
*
U series
*
U series
*
U series
*
Communication type
TU2C-Link
TCC-Link
Maximum number
of connectable units
16
8
* Other than U series
¡
Communication type, model names and the maximum
number of connectable units
¡
- 15 -