Codes (DN codes) for changing settings
Codes in the table below are necessary for local advanced control.
* Adjusting this setting is necessary for the header unit when using a system equipped with the Air to Air Heat Exchanger
with DX Coil Unit only, and the Air to Air Heat Exchanger with DX Coil Unit with the smallest indoor unit address number
when using a system equipped with the Air to Air Heat Exchanger with DX Coil Unit and air conditioners.
Code
Description
SET DATA and description
Factory default
Note
01
Lighting-up hours of
the Filter Sign
0000: None
0001: 150 H
0002: 2500 H
0003: 5000 H
0004: 10000 H
0002: 2500 H
Adjusting this setting is
necessary for the header unit.
06
Detect temperature
shift value when
heating
0000: No shift
0001 – 0006:
[SET DATA value] × 1 °C shift
0002: 2 °C shift
31
Single operation of
the fan
0000: Invalid
0001: Valid
ON/OFF operation for the Air to Air
Heat Exchanger with DX Coil Unit only
0000: Invalid
Adjusting this setting is
necessary for the header unit.
(System equipped with the Air to
Air Heat Exchanger with DX Coil
Unit and air conditioners)
32
Remote controller
sensor
0000: Do not use
0001: Use
0000: Do not use
48
Unbalanced
ventilation Fan
speed
0000: Normal
0001: SA (High) > EA (Low) active
0002: SA (Low) < EA (High) active
* “High” may be “Extra High”.
0000: Normal
Adjusting this setting is
necessary for all the Air to Air
Heat Exchanger with DX Coil
Units in the group.
4C
Nighttime heat
purge
0000: Invalid
0001-0048: Start after [Setting value] x
1 hour(s)
* Setting for the time before the
nighttime heat purge operation starts
0000: Nighttime
heat purge
OFF
Adjusting this setting is
necessary for all the Air to Air
Heat Exchanger with DX Coil
Units in the group. (System
equipped with the Air to Air Heat
Exchanger with DX Coil Unit and
air conditioners)
4E
Setting of the linked
operation with
external devices
0000: ON/OFF linked
0001: ON linked
0002: OFF linked
* Specifies whether the ON/OFF
operation of the Air to Air Heat
Exchanger with DX Coil Unit is linked
with the external device operation
0000: ON/OFF
linked
Adjusting this setting is
necessary for a Air to Air Heat
Exchanger with DX Coil Unit to
which an adapter for remote ON/
OFF control (sold separately) is
connected.
EA
Changing the
ventilation mode
0002: Heat Exchange mode
0003: Automatic mode
* Compatible with systems without a
remote controller and RBC-AMT32E
0003: Automatic
mode
*1
EB
Changing the
ventilation Fan
speed
0002: High
0003: Low
0004: Unbalanced
* “High” may be “Extra High”.
* Compatible with systems without a
remote controller and RBC-AMT32E
0002: High
*1
ED
Changing the
operation output
0000: ON during normal operation
0001: ON during normal operation or
nighttime heat purge operation
0002: ON during nighttime heat purge
operation
0003: ON when SA fan is running
0004: ON when EA fan is running
0000: ON during
normal
operation
Adjusting this setting is
necessary for a Air to Air Heat
Exchanger with DX Coil Unit
which transfers the operation
output.
EE
Changing the
abnormal signal /
Bypass mode
signal output
0000: ON when an abnormal signal is
detected
0001: ON when the Bypass mode
signal is detected
0000: ON when an
abnormal
signal is
detected
Adjusting this setting is
necessary for a Air to Air Heat
Exchanger with DX Coil Unit
which transfers the operation
output.
Group control
In a group control, a remote controller can control up to maximum 8 units.
• For wiring procedure and wiring method of the individual line (Identical refrigerant line) system, refer to “Electric
wiring” in this Manual.
• Wiring between indoor units in a group is performed in the following procedure.
Connect the indoor units by connecting the remote controller inter-unit wires from the remote controller terminal
blocks (A/B) of the indoor unit connected with a remote controller to the remote controller terminal blocks (A/B)
of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual attached to the outdoor unit.
Changing the time before the Filter Sign lights up
The time before the Filter Sign lights up can be changed according to the installation conditions.
* Adjust this setting for the header unit.
• Select [01] in step 3 on page 70.
• Select a value from the table on the below in step 4 on page 70 according to the preferred time before the
Filter Sign lights up.
For better heating performance
When it is hard to become hot due to the location of the indoor unit, room structure, etc., you can raise the detect
temperature for heating. It is recommended that you use a circulator or the like to circulate warm air around the
ceiling.
• Select [06] for CODE NO. in Step 3 on page 70.
• Select CODE NO. from the following table in Step 4 on page 70:
* In addition to the above detect temperature shift value, the own detect temperature shift value (Heat: 2.5 °C,
Cool: -2.0 °C) is set for the Air to Air Heat Exchanger with DX coil unit in order to intake enough outdoor air. This
setting does not need to be changed, but if you want to change the setting, contact our Customer Support Center.
Code
SET DATA
0000
0001
0002
0003
0004
01
Time before the Filter
Sign lights up
None
150H
2500H
(Factory default)
5000H
10000H
Code
SET DATA
0000
0001
0002
0003
0004
0005
0006
06
Detect temperature
Shift value
None
+ 1 °C
+ 2 °C
(default)
+ 3 °C
+ 4 °C
+ 5 °C
+ 6 °C