– 80 –
How to check
To display an error code or to confirm the operation status, the remote controller (wired remote controller and
central remote controller) is equipped with an LCD display, and the interface circuit board of the outdoor unit is
equipped with a 7 segment display. A self-diagnosis function is activated to find out the details of a problem with
the unit.
Error code list
The table below shows the error codes. See the table for details of error codes.
• To confirm the code from the remote controller, see “Wired remote controller display” in the table.
• To confirm the code from the outdoor unit, see “7 segment display on the outdoor unit” in the table.
Wired
remote
controller
display
Check code
Check code name
Judging
device
7 segment display on the
outdoor unit
Auxiliary code
E01
—
—
Indoor unit - remote controller communication error (Detected by
remote controller)
Remote
controller
E02
—
—
Remote control transmission error
Remote
controller
E03
—
—
Indoor unit - remote controller communication error (Detected by indoor
unit)
Indoor
E04
—
—
Indoor / Outdoor unit communication circuit error (Detected by indoor
unit)
Indoor
E06
E06
Number of indoor units for
normal reception
Number of indoor units decreasing
I/F
—
E07
—
Indoor / Outdoor unit communication circuit error (Detected by outdoor
unit)
I/F
E08
E08
Duplicate indoor addresses Duplicate indoor addresses
Indoor I/F
E09
—
—
Duplicate header remote controllers
Remote
controller
E10
—
—
Indoor MCU communication error
Indoor
E12
E12
01: Indoor / Outdoor unit
communication
02: Communications
between outdoor units
Automatic address start error
I/F
E15
E15
—
No indoor unit during automatic address
I/F
E16
E16
00: Over capacity
01
~
: Number of connected
units
Number of connected units / Over capacity
I/F
E18
—
—
Indoor header - follower communication error
Indoor
E19
E19
00: No center unit
02: Multiple center units
Unusual number of center outdoor units
I/F
E20
E20
01: Outdoor connections of
another line
02: Indoor connections of
another line
Connections of another line during automatic address
I/F
E21
E21
02: No header unit
00: Number of duplicate
header units
Unusual number of thermal header units
I/F
E22
E22
—
Number of thermal units decreasing
I/F
E23
E23
—
Transmission error between outdoor units Number of thermal units error
(Reception error)
I/F
E25
E25
—
Duplicate terminal outdoor address settings
I/F
E26
E26
Number of outdoor units for
normal reception
Number of connected outdoor units decreasing
I/F
E28
E28
Detected outdoor unit No.
Terminal outdoor error
I/F
E31
E31
IPDU communication error
I/F
F01
—
—
Indoor TCJ sensor error
Indoor
F02
—
—
Indoor TC2 sensor error
Indoor
F03
—
—
Indoor TC1 sensor error
Indoor
F04
F04
—
TD1 sensor error
I/F
F05
F05
—
TD2 sensor error
I/F
F06
F06
01: TE1 02: TE2
TE1 sensor error
I/F
F07
F07
01: TE1 02: TE2
TL sensor error
I/F
F08
F08
—
TO sensor error
I/F
F10
F10
—
Indoor TSA sensor error
Indoor
F11
—
—
Indoor TFA sensor error
Indoor
F12
F12
—
TS1 sensor error
I/F
F13
F13
01: Compressor 1
02: Compressor 2
03: Compressor 3
TH sensor error
IPDU
F15
F15
—
Miswiring of outdoor temperature sensor (TE, TL) error
I/F
F16
F16
—
Miswiring of outdoor pressure sensor (Pd, Ps)
I/F
F17
—
—
Indoor TOA sensor error
Indoor
F18
—
—
Indoor TRA sensor error
Indoor
F22
F22
—
TD3 sensor error
I/F
F23
F23
—
Ps sensor error
I/F
F24
F24
—
Pd sensor error
I/F
F29
—
—
Indoor unit or other error
Indoor
F31
F31
—
Outdoor EEPROM error
I/F
H01
H01
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor breakdown
IPDU
H02
H02
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor error (Lock)
IPDU
H03
H03
01: Compressor 1
02: Compressor 2
03: Compressor 3
Current detection circuit error
IPDU
H05
H05
—
Miswiring of outdoor discharge temperature sensor (TD1)
I/F
H06
H06
—
Low-pressure protection activation
I/F
H07
H07
—
Lower oil level detection protection
I/F
Wired
remote
controller
display
Check code
Check code name
Judging
device
7 segment display on the
outdoor unit
Auxiliary code
○
: IPDU error
A3-IPDU
Fan IPDU
1
2
3
01
○
02
○
03
○
○
04
○
05
○
○
06
○
○
07
○
○
○
08
○
09
○
○
0A
○
○
0B
○
○
○
0C
○
○
0D
○
○
○
0E
○
○
○
0F
○
○
○
○
159-EN
160-EN