– 56 –
2
Accessory parts
Separately sold parts
The remote controller (NRC-01HE) is sold separately. For the installation of these products, follow the installation
manual supplied with it.
Name
Quantity
Shape
Usage
Installation manual
1
This manual
(Be sure to hand it to the customers.)
CD-ROM
(Owner’s manual,
Installation manual)
1
—
(For other languages that do not appear in this manual,
please refer to the enclosed CD-ROM.)
Owner’s manual
1
—
(Be sure to hand it to the customers.)
Insulation
(VNK type only)
1
For strainers
Insulation
4
For insulation of hanging brackets
Insulation
(VNK type only)
1
For water supply pipes
Duct connectors
4
Connector with ducts
Screws
24
For duct connectors
Banding band
4
For anchoring the insulated pipes
Heat insulator
2
For heat insulation of pipe connecting section
3
Restrictions on system construction
System combinations available
The Air to Air Heat Exchanger with DX Coil Unit can be connected to a Super Module Multi system -i and Super
Heat Recovery Multi-i (SHRM-i).
Range of combination
1. The Air to Air Heat Exchanger with DX Coil Unit can be connected with either one of the following multi systems:
• System with Air to Air Heat Exchanger with DX Coil Unit and air conditioner indoor units
• Air to Air Heat Exchanger with DX Coil Unit system
2. The overall capacity (HP) of air conditioner indoor units and Air to Air Heat Exchanger with DX Coil Unit should
be 80 to 135% of that of outdoor units.
3. When calculating the connection capacity of the indoor unit, use the following horse power:
System with Air to Air Heat Exchanger with DX Coil Unit and air conditioner indoor units
Air to Air Heat Exchanger with DX Coil Unit system
The Air to Air Heat Exchanger with DX Coil Unit and the concealed duct type fresh air intake unit cannot be used
together in the same system.
Model name
MMD-
VNK502HEX1E
VN502HEX1E
VNK802HEX1E
VN802HEX1E
VNK1002HEX1E(2)
VN1002HEX1E(2)
HP
1.0
1.7
2.0
Air conditioner indoor units
Air to Air Heat Exchanger
with DX Coil Unit
In case of SHRM-i, Air to Air Heat Exchanger
with DX Coil Unit should be 0 to 30% of the
capacity of air conditioner indoor units.
Air to Air Heat Exchanger with DX Coil Unit
* It is impossible to use only SHRM-i and Air
to Air Heat Exchanger with DX Coil Unit
together in the same system.