(1) Power supply abnormality (alert code "1")
CAUTION
●
Fully pay attention to electric shock when checking the power supply.
●
When checking fuses, turn "OFF" the power switch on the operating panel and further
disconnect the power cable from the ship
’s distribution board before checking fuses.
1. Confirm power applying state of the power supply.
Confirm the automatic steering system type according to the finished plan of this
ship.
1-1. One gyrocompass system
(1) Stand alone type (Model TG-8100/8600-S)
The system where both of the master compass and the control unit are not
built in the automatic steering system.
Input terminals of the main power supply (between 1AC1 and 1AC2 of the
external terminal board TB101 in the control unit)
Voltage: 100 / 110 / 115 / 220 V AC, within
±
10 %
Frequency: 50 / 60 Hz, within
±
5 %
Input terminals of the emergency power supply (between 1B+ and 1B- of the
external terminal board TB101)
Voltage: 24 V DC, within -20 % to +30 %
(2) Automatic steering system built-in type
①
(Model PR-9
□
1
□
D / PR-9
□
1
□
E)
The system where both of the master compass and the control unit are built
in the automatic steering system.
Input terminals of the main power supply (between 1AC1 and 1AC2 of the
external terminal board TB101 in the control unit)
Voltage: 100 / 110 / 115 / 220 V AC, within
±
10 %
Frequency: 50 / 60 Hz, within
±
5 %
Input terminals of the emergency power supply (between 1B+ and 1B- of the
external terminal board TB101)
Voltage: 24 V DC, within -20 % to +30 %
1-2. Two gyrocompasses system
(1) Stand alone type (Model TG-8100/8600-D)
The system where the master compass and the control unit for two
gyrocompasses are not built in the automatic steering system.
No. 1 gyrocompass side
Input terminals of the main power supply (between 1AC1 and 1AC2 of the
external terminal board TB101 in the control unit)
Voltage: 100 / 110 / 115 / 220 V AC, within
±
10 %
Frequency: 50 / 60 Hz, within
±
5 %
Input terminals of the emergency power supply (between 1B+ and 1B- of the
external terminal board TB101 in the control unit)
Voltage: 24 V DC, within -20 % to +30 %
Summary of Contents for TG-8000 Series
Page 2: ......
Page 20: ...18 blank...
Page 26: ...1 6 blank...
Page 60: ...3 28 blank...
Page 84: ...6 2 blank...
Page 86: ...7 2 CONTROL UNIT OPERATING UNIT Fig 7 1 Outline of control unit One Gyro compass system...
Page 88: ...7 4 Fig 7 3 Master compass FUSE F1 12A...
Page 96: ...7 12 Power Supply Unit Fig 7 11 Power Supply Unit...
Page 98: ...7 14 blank...
Page 104: ......