Page 5-14
Document Ref 942583-001 Rev 8
Installation
Quantium 510 Installation Manual
9)
Raise the dispenser approximatley 20mm off the
ground and using a 19mm spanner or socket,
loosen and remove the bolts holding the end pallet
sections. Remove the wooden end sections from
both sides of the dispenser.
10) Carefully position the dispenser over the
cradle so that the filter boxes are directly
above the fuel supply risers. Lower the
dispenser slowly, aligning the mounting holes
on the driptray with the mounting holes on
the cradle.
11) Use the mounting hole closest to the hydraulic
end as a first locating point.
Follow the instructions in section 5.4.8 to
secure the dispenser using all 4 mounting
holes.
12) With the dispenser now secure, remove the retaining ratchet straps.
Ensure that the area around the dispenser is clear of all personnel, then slowly
remove the forklift and move it away from the dispenser.
13) Using a rust preventative fluid, such as
Waxoyl professional 120-4 (Black), apply a
generous coating to the inside and outside of
the forklift slots.
14) Fit the supplied blanking plates to all 4 slots in
the driptray and apply a coat of rust
preventative around the 4 edges of each
blanking plate.
Dispenser placement is complete.