Document Ref 942583-001 Rev 8
Page 5-25
Quantium 510 Installation Manual
Installation
5.5
Hydraulic Connections
Connect all hydraulic and electric junctions according to the specifications as described in
this section and indicated on the drawings in Section 3.
Flow rates achieved are dependent upon the type of submerged pumping system used and
other site-specific conditions.
Note : The maximum pressure must not exceed 3.5 bar.
5.5.1
INSTALLATION OF TQP-HS PUMPS
IMPORTANT INFORMATION:
DO NOT INSTALL TQP-HS PUMPS, 80 OR 130 LPM, IN SERIES ON
THE SAME SUCTION LINE.
SEPARATE SUCTION LINES ARE REQUIRED, AS EXAMPLES
SHOW BELOW:
5.5.2
PIPEWORK - SUCTION DISPENSERS
Connections to the fuel supply pipes and the vapour return lines are accessible
from side B of the dispenser (see section 5.2 for identification of sides).
The dispenser is positioned with the filter box positioned above the relevant fuel
supply risers. If required, adapters should be fitted to the supply pipes. The
flexible connection (rigid for pressurised systems) should then be fitted between
the fuel supply risers and the filter box.
PUMPING UNITS WITH EXTERNAL FILTER BOX
1)
Remove the protective covers on the fuel supply riser
pipe and on the filter box.
WARNING : BEWARE OF FUEL SPILLAGE.
2)
Cut the rubber manchet to suit the riser pipe diameter
and fit over the pipe to cover the hole in the driptray.
TQP-HS
80
TQP-HS
80
9.6 m³/h
160 l/min