8-2
Application and Configuration Examples
•
Status LED is green. Refer to "Status indicator" on page 10-1 for an explanation of the dis-
play codes.
2. Start OMNI LINK on the PC.
3. Choose
Cancel
from the Drive Select dialog box.
4. Select
PC Set Up
from the Communications menu in OMNI LINK to display the personal com-
puter’s communication settings.
5. Verify the communications port settings of the PC match those of the drive.
•
If the settings are correct, select
OK
in the Port – Settings dialog box.
•
If the settings are different, correct the Port – Settings to allow communications with the
drive.
Factory default communications Port – Settings for the drive are:
– Baud Rate:
9600
– Data Bits:
8
– Parity:
None
– Stop Bits:
1
– Serial Port:
COM1
Refer to the section “RS-232 Communication Test” on page 11-6 for troubleshooting instructions.
6. Select
Read Drive Parameters
from the Communications menu.
7. Verify the Drive Name and Address are correct for the drive that is being addressed.
8. Choose
OK
to load the drive parameters.
9. If the message box appears that a motor must be selected, select
OK
. The Drive Set Up window
is displayed with Motor Model selection parameter active. The motor may be selected from the
Intro
F
IGURE
8.1
Analog Controller Connection Diagram
TIP
A motor must be selected for the parameters to load.
J1
26 I/O PWR
20 ENABLE
21 FAULT
22 CMND+
23 CMND-
Close to ENABLE Drive
Close to RESET Fault
±10VDC
DRIVE
L1 3
L2/N 4
Gnd 5
100-240 VAC
50/60 Hz
Single Phase
Power Source
RESET
J5
2 RCV
3 XMT
5 COM
XMT
RCV
COM
TB1
Phase R 6
Phase S 7
Phase T 8
Mtr Gnd 9
J2
Motor
Encoder
External I/O
12-24 VDC
Power Source
5 I/O PWR
6 I/O COM