Inspection Troubleshooting
Problem
Cause
Remedy
A return air
temperature
reading is not
within desired
temperature
range of the
setpoint.
The unit has not
had time to cool
down to correct
temperature.
Refer to the load log history. Look for above temperature load records,
properly pre-cooled cargo compartment, length of time on road, etc. Correct
as required. Continue monitoring return air temperature until the reading is
within the desired temperature range of the setpoint.
The unit may have
a low refrigerant
charge.
Check the receiver tank sight glass for refrigerant level. If liquid is not
showing in the receiver tank sight glass, the refrigerant charge may be low.
A competent refrigeration technician is required to add refrigerant or repair
the system. Contact the nearest Thermo King dealer, authorized Service
Center, or call the Thermo King Cold Line for referral. Consult the Table of
Contents for Cold Line information.
The unit is in defrost
or has just
completed a defrost
cycle.
Monitor the return air temperature after the defrost cycle is completed to see
if the temperature returns to the desired temperature range of the setpoint.
The evaporator is
plugged with frost.
Initiate a manual defrost cycle. The defrost cycle will automatically terminate
when complete. Continue monitoring the return air temperature until the
reading is within the desired temperature range of the setpoint.
Loading and Enroute Inspections
87
Inspection Troubleshooting
Problem
Cause
Remedy
A return air
temperature
reading is not
within desired
temperature
range of the
setpoint.
The unit has not
had time to cool
down to correct
temperature.
Refer to the load log history. Look for above temperature load records,
properly pre-cooled cargo compartment, length of time on road, etc. Correct
as required. Continue monitoring return air temperature until the reading is
within the desired temperature range of the setpoint.
The unit may have
a low refrigerant
charge.
Check the receiver tank sight glass for refrigerant level. If liquid is not
showing in the receiver tank sight glass, the refrigerant charge may be low.
A competent refrigeration technician is required to add refrigerant or repair
the system. Contact the nearest Thermo King dealer, authorized Service
Center, or call the Thermo King Cold Line for referral. Consult the Table of
Contents for Cold Line information.
The unit is in defrost
or has just
completed a defrost
cycle.
Monitor the return air temperature after the defrost cycle is completed to see
if the temperature returns to the desired temperature range of the setpoint.
The evaporator is
plugged with frost.
Initiate a manual defrost cycle. The defrost cycle will automatically terminate
when complete. Continue monitoring the return air temperature until the
reading is within the desired temperature range of the setpoint.
Summary of Contents for SB-200TG
Page 1: ...Operator s Manual SB 200TG Operator s Manual SB 200TG TK 53598 2 OP Rev 0 02 07...
Page 7: ...6 Table of Contents 6...
Page 11: ...10 Introduction 10...
Page 21: ...20 EPA Emission Control System Warranty Statement 20...
Page 43: ...42 TG VI Controller Description 42...
Page 45: ...44 Remote Status Light Optional 44...
Page 83: ...82 Alarm Codes 82...
Page 103: ...102 Warranty 102...
Page 117: ...116 Serial Number Locations 116...