Unit Operation with TG-VI Controller
56
Initiating a Manual Defrost Cycle
1.
The unit must be running in Continuous or
CYCLE-SENTRY mode or be in CYCLE-SENTRY Null
mode and the coil temperature must be below 45 F (7 C).
2.
Press the
S
ELECT
key until the
dEF
(defrost) prompt
appears in the display.
3.
Press the
E
NTER
key to enter a Defrost cycle. The display
will briefly show
Lod
(load). The unit will then enter a
Defrost cycle. The Defrost cycle will terminate
automatically.
NOTE: The
E
NTER
key must be pressed to enter a Defrost
cycle. The display will return to the Standard Display in
about 10 seconds and the defrost mode will not be entered
unless the
E
NTER
key is pressed.
1.
Select Key
2.
Enter Key
Figure 25: Initiating a Manual Defrost Cycle
AMA60
1
2
Unit Operation with TG-VI Controller
56
Initiating a Manual Defrost Cycle
1.
The unit must be running in Continuous or
CYCLE-SENTRY mode or be in CYCLE-SENTRY Null
mode and the coil temperature must be below 45 F (7 C).
2.
Press the
S
ELECT
key until the
dEF
(defrost) prompt
appears in the display.
3.
Press the
E
NTER
key to enter a Defrost cycle. The display
will briefly show
Lod
(load). The unit will then enter a
Defrost cycle. The Defrost cycle will terminate
automatically.
NOTE: The
E
NTER
key must be pressed to enter a Defrost
cycle. The display will return to the Standard Display in
about 10 seconds and the defrost mode will not be entered
unless the
E
NTER
key is pressed.
1.
Select Key
2.
Enter Key
Figure 25: Initiating a Manual Defrost Cycle
AMA60
1
2
Summary of Contents for SB-200TG
Page 1: ...Operator s Manual SB 200TG Operator s Manual SB 200TG TK 53598 2 OP Rev 0 02 07...
Page 7: ...6 Table of Contents 6...
Page 11: ...10 Introduction 10...
Page 21: ...20 EPA Emission Control System Warranty Statement 20...
Page 43: ...42 TG VI Controller Description 42...
Page 45: ...44 Remote Status Light Optional 44...
Page 83: ...82 Alarm Codes 82...
Page 103: ...102 Warranty 102...
Page 117: ...116 Serial Number Locations 116...