MP-3000a Controller
92
•
Set Log Time: Sets the data log interval (1
minute or 1/2, 1, 2 or 4 hours).
•
Activate Trip start: Sets the date and time of
the trip start.
•
Inspect PTI Log: Displays results of last PTI
test including component volt and amps data
and sensor temperatures. Test values are
recorded at the start and end of the Chilled and
Frozen Mode test.
Viewing the Datalogger Menu
With the unit On/Off switch ON and the LCD display show-
ing the standard display (setpoint):
1. Press the F3 key to enter the Main Menu.
2. Press F2 key to scroll through Main Menu
until “DATA-LOGGER” appears in LCD
display.
3. Press F4 key to access the Datalogger menu.
The first function appears in the LCD display:
Inspect Temp Log.
4. Press F2 or F3 key to scroll to the desired
function:
- Inspect Temp Log
- PTI State
- Inspect Event Log
- Set Log Time
- Activate Tripstart
- Inspect PTI Log
5. Press F4 key to access the function selected.
Inspect Temp Log
With the unit On/Off switch ON and the LCD
display showing the standard display (setpoint):
1. Press the F3 key to enter the Main Menu.
2. Press F2 key to scroll through Main Menu
until “DATA-LOGGER” appears in LCD
display.
3. Press F4 key to access the Datalogger menu.
“Inspect Temp Log” appears in the LCD
display.
4. Press F4 key to enter Temp Log. LCD display
shows the Log Time and the Setpoint, Supply
and Return temperatures of the most recent
log in the first screen.
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...