![background image](http://html.mh-extra.com/html/thermo-king/crr-40-119/crr-40-119_manual_1104388082.webp)
MP-3000a Controller
82
Function Test
The MP-3000a controller contains a special
function test that automatically tests individual
components including the controller display,
sensors, condenser fan, evaporator fan,
compressors, etc. The test includes measurement
of component power consumption and compares
test results to expected values.
NOTE: The Function Test does not test the
actual performance of the complete system.
Therefore it is not a Pretrip test and should not
be used instead of the PTI Test.
With the unit On/Off switch ON and the LCD
display showing the standard display (setpoint):
1. Press F3 key to enter the menu list.
Repeatedly press F2 key to scroll through
Main Menu until “COMMANDS” appears in
LCD display.
2. Press F4 key to access the Commands menu.
The first command in the submenu appears in
the LCD display.
3. Press F2 or F3 key to scroll to Function Test.
4. Press F4 key to start the Function Test. LCD
display shows functional test currently being
performed. Function test ends automatically.
Unit automatically returns to normal
operation. See “CRR Function Test” on page
82.
CRR Function Test
LED
Display
(Test No.)
LCD Display
(Shows Approx.
Amps for 460V,
60 Hz Unit)
Test Description
Possible
Alarms
Duration
(Time)
F1.00
Display Test
Activated
0.1A 0.0A0.1A
Event Log for Function Test begins.All alarms are
turned OFF. Alarm list is cleared. All lights and bars
in display turn ON.
None
10 Seconds
F1.01
Sensor Test
Activated
0.1A 0.0A 0.1A
All Sensors must have values within their
measuring range.
00 01, 02, 03,
04, 05, 32,
33, 34, 35,
97, 98, 109,
110, 112
2 Seconds
F1.02
Evaporator Fan
Low Activated
1.1A 1.0A 1.1A
Amp draw is measured and compared to voltage
and frequency. CRR40
1.0 Amps approx. at 50 Hz
1.0 Amps approx. at 60 Hz
14, 15
10 Seconds
F1.03
Evaporator Fan
High Activated
2.4A 2.3A 2.4A
Amp draw is measured and compared to voltage
and frequency
CRR40
2.1 Amps approx. at 50 Hz
2.5 Amps approx. at 60 Hz
12, 13
10 Seconds
F1.04
Condenser Fan
Activated
0.8A 0.7A 0.8A
Amp draw is measured and compared to voltage
and frequency: 0.8 Amps.
16, 17
10 Seconds
F1.05
Reverse Phase
Activated
08.A 0.7A 0.8A
Condenser fans stops. Reverse phase selector
relay is energized and condenser motor is started in
reverse for 2 seconds. Amp draw difference
between correct and wrong motor rotation must be
less than 0.2 amps
58
30 Seconds
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...