151
Diagnosis
Mechanical Diagnosis
Condition
Possible Cause
Remedy
Compressor does not
operate- no amperage draw
Controller ON; unit start sequence still
timing
Wait up to 3 minutes for compressor
start-up
No Power to unit (condenser and
evaporator fans do not operate)
Locate fault and repair: power source,
power plug, main circuit breaker, motor
contactor, motor terminals, motor
Open in 29 VAC control circuit
Check fuses and On/Off switch. Replace
or repair as required.
Container temperature does not
demand compressor operation
Adjust controller setpoint
Compressor contactor inoperative
Replace compressor contactor
No output signal from controller
Diagnose and replace main relay board
or controller
Unit on defrost
Turn unit On/Off switch OFF and then
ON again
Defective high pressure cutout switch
Replace high pressure cutout switch
High condenser head pressure
causing high pressure cutout
Check refrigeration system and correct
fault
Defective compressor
Replace compressor
Controller shut unit down on
Compressor Over Temperature (fault
code 56)
Let compressor cool and controller will
reset automatically. Check liquid
injection valve and compressor
temperature sensor
Compressor motor internal thermal
overload protection open
If compressor contactor is energized,
wait 60 minutes for protector to cool and
reset
Compressor does not
operate; excessive
amperage draw or
intermittent cycling on
overload
NOTE: Controller
sequence starts the
compressor when the unit
has been off for more than
18 hours.
Piston stuck
Remove compressor head. Look for
broken valve and jammed parts
Seized or frozen compressor bearings
Replace compressor
Improperly wired
Check/correct wiring against wiring
diagram
Low line voltage
Check line voltage-determine location of
voltage drop
High head pressure
Eliminate cause of high head pressure
Contacts in compressor contactor not
closing completely
Check by operating manually. Repair or
replace
Open circuit in compressor motor
winding
Check motor stator connections. Check
stator winding for continuity. If open,
replace compressor
Defective compressor motor internal
thermal overload protector
Replace thermal overload protector or
compressor
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...