MP-3000a Controller
115
Code
Description
Corrective Action
33
Ambient Air Sensor Open Circuit (Check Alarm)
• Sensor circuit resistance higher than 100,000
ohms.
• Temperatures below -70 C(-94 F).
• Indicates:
• Sensor circuit resistance lower than 200
ohms.
• Temperature above 80 C (176 F).
• Indicates:
• Short circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 13 and
14 on plug J15. Resistance must be 2,000 ohms
at 25 C (77 F).
• Check cable no. 1 between controller and relay
board.
34
Ambient Air Sensor Open Circuit (Check Alarm)
• Sensor circuit resistance higher than 100,000
ohms.
• Temperature below -70 C (-94 F).
• Indicates:
-Open circuit to sensor
-Defective or wrong sensor
-Defective relay board
-Defective cable No.1
-Defective controller
• Check sensor resistance between pins 13 and
14 on plug J15. Resistance must be 2,000 ohms
at 25 C (77 F).
• Check cable No.1 between controller and relay
board
35
Ambient Air Sensor Short Circuit (Check Alarm)
• Sensor circuit resistance lower than 200 ohms.
• Temperature above 80 C(176 F).
• Indicates:
-Short circuit to sensor
-Defective or wrong sensor
-Defective relay board
-Defective cable No.1
-Defective controller
• Check sensor resistance between pins 13 and
14 on plug J15. Resistance must be 2,000 ohms
at 25 C (77 F).
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...