MP-3000a Controller
119
Code
Description
Corrective Action
111
KVQ Heat Error (Check Alarm)
• KVQ valve actuation temperature is not in range
within preset time.
• Indicates:
• Disconnected CB7A
• Defective heat element in valve actuator
• Inaccurate actuator temperature
measurement
• Defective relay board
• Defective circuit between pin 4 and 6 on plug
J11 (KVQ actuator requires power from both
relays 2 and 3)
• Defective cable No. 2
• Defective controller
• Carefully inspect actuator:
If actuator is hot, check that the actuator sensor
has been mounted correctly in p ins 11 and 12
on plug J15.
If actuator is not hot, check resistance between
pins 5 and 6 on plug J11. Resistance must be
about 17 Ohms. Check voltage from pins 5 and 6
(relays 2 and 3).
• Check cable No. 2 between controller and relay
board.
112
Zero Current Too High (Check Alarm)
• Ground (zero current) circuit 30 milliamps.
• Indicates:
• Defective motor or heater insulation to ground
• Enter Manual Function Test manual and test
(operate) each motor and heater separately. not
when alarm occurs.
115
Probe Error (Check Alarm)
• Occurs during Pretrip (PTI) test or Probe Test
failed in Chilled mode
• Temperature difference between return air and
evaporator coil sensors is too high (1.5 C [2.7 F]
difference maximum)
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
2,000 ohms at 25 C (77 F).
• Check left hand and right hand supply air sensor
locations.
116
Probe Error (Check Alarm)
• Occurs during Pretrip (PTI) test or Probe Test
failed in CHilled mode
• Temperature difference between return air and
supply air sensors is too high (0.8 C[1.5 F]
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
2,000 ohms at 25 C (77 F).
• Check left hand and right hand supply air sensor
locations.
117
Probe Error (Check Alarm)
• Occurs during Pretrip (PTI) test or Probe Test
failed in CHilled mode
• Temperature difference between LH supply and
RD supply sensors is too high (0.5 C [1.0 F]
difference maximum)
• Indicates:
• Incorrect temperature reading on one sensor
• Supply air sensor not placed in air flow stream
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
2,000 ohms at 25 C (77 F).
• Check left hand and right hand supply air sensor
locations.
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...