MP-3000a Controller
98
NOTE: Be certain that all connector plugs
carefully seated.
CAUTION: Be sure to enter the container ID
before releasing the unit for service. The
container ID is required to identify the data
downloaded from the controller datalogger via a
lap-top computer or a REFCON remote
communications system.
NOTE: Several programmable features may
need to be set to completely configure the unit to
customer specifications. Adjust any additional
programmable settings to customer requirements
before releasing the unit for service.
NOTE: If a controller from another unit has
been installed, see “Controller Software
Selection” in this chapter to set software
selection dial correctly.
Automatic Configuration of Spare
Parts Controller
An automatic configuration feature detects the
unit options installed on a unit when a spare parts
controller is installed in the unit and powered up
for the first time. After the initial unit power up,
the controller turns the Auto Configuration feature
Off.
The Auto Configuration feature detects the
following options and sets the correct value in
Configuration menu:
•
Number of Supply Air Sensors (1 or 2):
Controller detects left hand and right supply
air sensors.
•
Number of Evaporator Fans (2 or 3)
•
Dehumidify (On or OFF): If controller detects
a humidity sensor, it then checks for current
draw on a dehumidify valve.
•
Humidification (On or OFF): If controller
detects a humidity sensor, it then checks for
current draw on an air compressor.
Controller Software Selection
If a replacement controller was removed from
another unit, check the small dial located on the
back of the controller for the correct software
selection. Current active software settings for dial
positions are:
•
Position 0: All TNE 508 units with Moduload
compressor
•
Position 1: All CRR-40/TNE 508 units with
KVQ valve
•
Position 2: All CSR20 PS, CSR40SL PS and
CSR40 PS units with a stepper motor valve
•
Position 7: Unit testing and service only.
Changing Software Selection Dial Position
1. Turn Unit On/Off switch OFF.
2. Set dial indicator to correct position.
3. Turn Unit On/Off switch ON. New software
selection is loaded during controller start-up.
Flash Loading Controller Software
Controller software must be flash loaded when
software has been revised. To flash load software:
1. Turn the unit On/Off switch OFF.
2. Plug cable from a portable computer with
controller software into the data retrieval
connector on the control box.
3. Press one of the special functions keys to
activate controller LCD display on battery
power; or turn the Unit On/Off switch ON.
4. Press and hold the “7” key and F1 key at the
same time. LCD display will show
“FLASHLOAD”.
NOTE: If the communications cable is defective
or not connected to the download port, the
controller will start in emergency mode and LCD
display will show “EMERGENCY MODE”.
Secure cable connection to proceed with flash
loading of software.
5. Start flash load program on portable
computer.
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...