MP-3000a Controller
107
Code
Description
Corrective Action
03
Return Air Sensor Short Circuit (Check Alarm)
• Sensor circuit resistance lower than 200 ohms.
• Temperature above 80C (176F).
• Indicates:
• Short circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No.1
• Defective controller
• Check sensor resistance between pins 3and 4
on plug J15. Resistance must be 2,000 ohms at
25C (77F).
• Check cable No.1 between controller and relay
board.
04
Evaporator Coil Sensor Open Circuit (Check
Alarm)
• Sensor circuit resistance higher than 100,000
ohms.
• Temperature below -70C (-94F).
• Indicates:
• Open circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No.1
• Defective controller
• Low evaporator coil temperature
• Check sensor resistance between pins 5 and 6
on plug J15. Resistance must be 2,000 ohms at
25C (77F).
• Check cable No.1 between controller and relay
board.
• Check evaporator air flow.
05
Evaporator Coil Sensor Short Circuit (Check
Alarm)
• Sensor circuit resistance lower than 200 ohms.
• Temperature above 80C (176F).
• Indicates:
• Short circuit to sensor
• Defective or wrong sensor
• Defective relay board
• Defective cable No. 1
• Defective controller
• Check sensor resistance between pins 5 and 6
on plug J15. Resistance must be 2,000 ohms at
25C (77F).
• Check cable No.1 between controller and relay
board.
Summary of Contents for CRR-40 119
Page 4: ......
Page 16: ...Safety Precautions 16...
Page 18: ...Service Guide 18...
Page 20: ...Model Features 20...
Page 32: ...Specifications 32...
Page 120: ...MP 3000a Controller 120...
Page 160: ...Wiring and Schematic Diagrams Index 160...
Page 161: ...161 MPC2000 Wiring Schematic...
Page 162: ...162 MPC2000 High Voltage Wiring Diagram...
Page 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Page 164: ...164 MPC2000 WCC Wiring Schematic...