OPERATION MENU’S
6. Maximum Spike Correction Table:
The maximum spike correction table is used to prevent large overshoot in special situation.
6.2.2.1 Tube
Configuration
Figure 6-18 Tube Configuration
The Tube Configuration Menu is used to set the type of thermocouples on the furnace, the
maximum heat up rate and the maximum profile deviation. The cursor position in
highlighted and the context sensitive information is displayed on line “Enter thermocouple
type (0-4)”. Confirming the selection with <RETURN> will move the cursor to the next
item automatically.
If an error is made the cursor can be moved back to a value using the <
> key.
The <
> and <
> allow the cursor to be moved to the left or right within the current
parameter, without altering any digit.
Spike Thermocouple Type:
To select the required thermocouple type, press the corresponding number (the possibilities
are shown on the upper right corner of the screen), followed by <RETURN>. If no changes
are required, press <RETURN> only. The cursor will automatically move to the paddle
thermocouple entry, which can be changed in the same way.
Operating Temperature Range:
The operating temperature range can be changed next and it must match the thermocouple
type. First enter the minimum temperature, followed by <RETURN>. Then enter the
maximum temperature.
T
OUCHSCREEN
R
EFERENCE MANUAL
6-16