54
・All specifications are subject to change without notice.
Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
HWS
50/ME
HWS50/ME Specifications
(Read instruction manual carefully, before using the power supply unit.)
ITEMS/UNITS
MODEL
HWS50-5/ME
HWS50-12/ME
HWS50-15/ME
HWS50-24/ME
HWS50-48/ME
Input
Voltage Range
(*2)
V
AC85 - 265 or DC120 - 370
Frequency
(*2)
Hz
47 - 63
Power Factor (100/200VAC)(typ) (*1)
0.99 / 0.95
Efficiency (100/200VAC)(typ)
(*1)
%
82 / 84
81 / 83
82 / 84
83 / 85
Current (100/200VAC)(typ)
(*1)
A
0.7 / 0.35
Inrush Current (100/200VAC)(typ) (*3)
A
14/28at, Ta=25
℃
, cold start
Leakage Current
(*10) mA
Less than 0.5. (0.2 (typ) at 100VAC / 0.4 (typ) at 230VAC)
Output
Nominal Voltage
VDC
5
12
15
24
48
Maximum Current
A
10
4.3
3.5
2.2
1.1
Maximum Power
W
50
51.6
52.5
52.8
Maximum Line Regulation
(*5) mV
20
48
60
96
192
Maximum Load Regulation
(*6) mV
40
96
120
192
384
Temperature Coefficient
Less than 0.02% /
℃
Maximum Ripple & Noise (0<Ta<70
℃
) (*4) mVp-p
120
150
200
Maximum Ripple & Noise (
−
10<Ta< 0
℃
) (*4) mVp-p
160
180
240
Hold-up Time (typ)
(*9)
ms
20
Voltage Adjustable Range
VDC
4.0 - 6.0
9.6 - 14.4
12.0 - 18.0
19.2 - 28.8
38.4 - 52.8
Function
Over Current Protection
(*7)
A
>10.5
>4.51
>3.67
>2.31
>1.15
Over Voltage Protection
(*8) VDC
6.25 - 7.25
15.0 - 17.4
18.8 - 21.8
30.0 - 34.8
55.2 - 64.8
Remote Sensing
-
Parallel Operation
-
Series Operation
Possible
Line DIP
Designed to meet SEMI-F47 (200VAC Line only)
Environment
Operating Temperature
(*11)
℃
-10 to +70 (-10 to +50: 100%, +60: 60%, +70: 20%)
Storage Temperature
℃
-30 to +85
Operating Humidity
%
RH
30 - 90 (No dewdrop)
Storage Humidity
%
RH
10 - 95 (No dewdrop)
Vibration
At no operating, 10 - 55Hz (sweep for 1min)
19.6m/s² constant, X, Y, Z 1hour each.
Shock (In package)
Less than 196.1m/s²
Cooling
Convection cooling
Isolation
Withstand Voltage
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min
Isolation Resistance
More than 100M
Ω
at 25
℃
and 70%RH Output - FG : 500VDC
Standards
Safety Standards
(*12)
Approved by UL60601-1, EN60601-1, CSA-C22.2 No.601.1-M90
PFHC
Designed to meet IEC61000-3-2
Voltage Fluctuations / Flicker Emissions
Designed to meet IEC61000-3-3
EMI
Designed to meet EN55011/EN55022-B, FCC-B, VCCI-B
Immunity
Designed to meet IEC61000-4-2(Level 3), -3(Level 3), -4(Level 3),
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (typ)
g
280
Size (W x H x D)
mm
26.5 x 82 x 120 (Refer to outline drawing)
(*1) At 100/200VAC, Ta=25
℃
and maximum output power.
(*2) For cases where conformance to various safety specs (UL, EN, CSA) are required,
to be described as 100 - 230VAC (50/60Hz).
(*3) Not applicable for the in-rush current to noise filter for less than 0.2ms.
(*4) Measure with JEITA RC-9131A probe, bandwidth of scope: 100MHz.
(*5) 85 - 265VAC, constant load.
(*6) No load-full load, constant input voltage.
(*7) Constant current limit and Hiccup with automatic recovery.
Not operate at over load or dead short condition for more than 30 seconds.
(*8) OVP circuit will shutdown output, manual reset (re power on).
(*9) At 100/200VAC, nominal output voltage and maximum output current.
(*10) Measured by the each measuring method of UL, EN and CSA (at 60Hz).
When using it as a patient care equipment, all outer surfaces of the equipment shall be constructed of
nonconductive material. See clause 19.5DV.2 of UL60601-1.
(*11) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve.
(*12) As for UL60601-1, EN60601-1 and CSA-C22.2 No.601.1-M90, basic insulation.
Please refer to "TDK-Lambda
EMC Filters" catalog.
●Recommended EMC Filter
RSEL-2001WL