(*1) Output voltage might be unstable when start up at -40 to -10
℃
and no load. In that case, apply minimum output current.
(*2) At 100/200VAC, Ta=25
℃
and maximum output power.
(*3) For cases where conformance to various safety specs (UL, CSA, EN) are required,to be described as 100 - 240VAC
(50/60Hz).
(*4) Not applicable for the in-rush current to noise filter for less than 0.2ms.
(*5) Measure with JEITA RC-9131A probe, bandwidth of scope :100MHz.
(*6) 85 - 265VAC, constant load.
(*7) No load-Full load, constant input voltage.
(*8) Constant current limit and hiccup with automatic recovery.
Not operate at over load or dead short condition for more than 30 seconds.
(*9) OVP circuit will shutdown output, manual reset (re power on).
(*10) At 100/200VAC, nominal output voltage and maximum output current.
(*11) Measured by the each measuring method of UL, CSA, EN and DENAN (at 60Hz).
(*12) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
- As for other mountings, refer to derating curve.
- For conditions of start up at -40
℃
to -10
℃
, refer to derating curve.
(*13) Category 4 exposure levels : Track transportation over U.S. highways, composite two-wheeled trailer.
(*14) As for DENAN, dsigned to meet at 100VAC.
ITEMS/UNITS MODEL HWS150-3/HD
HWS150-5/HD
HWS150-12/HD
HWS150-15/HD
HWS150-24/HD
HWS150-48/HD
Input
Voltage Range
(*3)
V
AC85 - 265 or DC120 - 370
Frequency
(*3) Hz
47 - 63
Power Factor (100/200VAC)(typ) (*2)
0.98 / 0.90
0.99 / 0.95
Efficiency (100/200VAC)(typ) (*2)
%
78 / 81
83 / 86
85 / 88
Current (100/200VAC)(typ)
(*2)
A
1.3 / 0.65
1.9 / 0.95
Inrush Current (100/200VAC)(typ) (*4)
A
14 / 28, Ta=25
℃
, cold start
Leakage Current
(*11) mA
Less than 0.5. (0.2 (typ) at 100VAC / 0.4 (typ) at 230VAC)
Output
Nominal Voltage
VDC
3.3
5
12
15
24
48
Minimum Current
(*1)
A
0.3
0.1
0.07
0.03
Maximum Current
A
30
13
10
6.5
3.3
Maximum Power
W
99
150
156
150
156
158.4
Maximum Line Regulation
(*6) mV
20
48
60
96
192
Maximum Load Regulation
(*7) mV
40
96
120
192
384
Temperature Coefficient
Less than 0.02% /
℃
Maximum Ripple & Noise (0<Ta<71
℃
) (*5) mVp-p
120
150
200
Maximum Ripple & Noise (
−
10<Ta
<
0
℃
) (*5) mVp-p
160
180
240
Hold-up Time (typ)
(*10) ms
20
Voltage Adjustable Range
VDC
2.97 - 3.96
4.0 - 6.0
9.6 - 14.4
12.0 - 18.0
19.2 - 28.8
38.4 - 52.8
Function
Over Current Protection
(*8)
A
>31.5
>13.6
>10.5
>6.82
>3.46
Over Voltage Protection
(*9) VDC
4.13 - 4.95
6.25 - 7.25
15.0 - 17.4
18.8 - 21.8
30.0 - 34.8
55.2 - 64.8
Remote Sensing
Possible
Parallel Operation
-
Series Operation
Possible
Line DIP
Designed to meet SEMI-F47 (200VAC Line only)
Environment
Operating Temperature
(*12)
℃
-10 to +71 (-10 to +50: 100%, +60: 60%, +71: 20%)
Guarantee start up at -40 to -10
Storage Temperature
℃
-40 to +85
Operating Humidity
%
RH
30 - 90 (No dewdrop)
Storage Humidity
%
RH
10 - 95 (No dewdrop)
Vibration (*13)
At no operating, 10 - 55Hz (sweep for 1min)
19.6m/s² constant, X, Y, Z 1hour each.
Designed to meet MIL-STD-810F 514.5 Category 4, 10
Shock (In package)
Less than 196.1m/s²
Designed to meet MIL-STD-810F 516.5 Procedure I, VI
Cooling
Convection cooling
Isolation
Withstand Voltage
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min
Isolation Resistance
More than 100M
Ω
at 25
℃
and 70%RH Output - FG : 500VDC
Standards
Safety Standards
(*14)
Approved by UL60950-1, CSA C22.2 No.60950-1, EN60950-1, EN50178
Designed to meet UL508, DENAN
PFHC Designed
to
meet
IEC61000-3-2
EMI
Designed to meet EN55011/EN55022-B, FCC-B, VCCI-B
Immunity
Designed to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3),
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (typ)
g
500
Size (W x H x D)
mm
37 x 82 x 160 (Refer to outline drawing)
Please refer to "TDK-Lambda
EMC Filters" catalog.
RSEL-2003W
●Recommended EMC Filter
HWS
150/HD
HWS150/HD Specifications
(Read instruction manual carefully, before using the power supply unit.)
38
・All specifications are subject to change without notice.
Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
Summary of Contents for HWS?HWS
Page 1: ...HWS Series AC DC Switching Power Supply HWS HWS ME HWS HD HWS P...
Page 30: ......
Page 68: ......