Please refer to "TDK-Lambda
EMC Filters" catalog.
●Recommended EMC Filter
RSEN-2016
HWS
1000/HD
ITEMS/UNITS
MODEL
HWS1000
-3/HD
HWS1000
-5/HD
HWS1000
-6/HD
HWS1000
-7/HD
HWS1000
-12/HD
HWS1000
-15/HD
HWS1000
-24/HD
HWS1000
-36/HD
HWS1000
-48/HD
HWS1000
-60/HD
Input
Voltage Range
(*2)
V
AC85 - 265 or DC120 - 330
Frequency
(*2) Hz
47 - 63
Power Factor (100/200VAC)(typ) (*1)
0.98/0.95
Efficiency (100/200VAC)(typ) (*1)
%
71/73
76/78
79/81
80/82
82/85
83/85
85/87
85/88
86/88
85/88
Current (100/200VAC)(typ)
(*1)
A
9.6/5.0
13.5/7.0
Inrush Current (100/200VAC)(typ) (*3)
A
20/40
Leakage Current (100/240VAC) (*10) mA
1.2 max
Output
Nominal Voltage
VDC
3.3
5
6
7.5
12
15
24
36
48
60
Maximum Current
A
200
167
134
88
70
46
30.7
23
18.4
Maximum Peak Current
(*13)
A
-
160
100
80
58.5
39
29.2
23.4
Maximum Power
W
660
1000
1002
1005
1056
1050
1104
Maximum Peak Power
(*13)
W
-
1200
1404
Maximum Line Regulation
(*5) mV
20
36
48
60
96
144
192
240
Maximum Load Regulation
(*6) mV
40
60
100
120
150
300
360
Temperature Coefficient
Less than 0.02% /
℃
Maximum
Ripple & Noise (*4)
0 to +71
℃
mVp-p
120
150
200
400
-10 to 0
℃
mVp-p
160
180
240
500
600
Hold-up Time (typ)
(*9) ms
20
Voltage Adjustable Range
VDC 2.64-3.96 4.0-6.0
4.8-7.2
6.0-9.0
9.6-14.4 12.0-18.0 19.2-28.8 28.8-43.2 38.4-52.8 48.0-66.0
Function
Over Current Protection
(*7)
A
>210.0
>175.3
>168.0
>105.0
>84.0
>61.4
>40.9
>30.6
>24.5
Over Voltage Protection
(*8) VDC 4.12-4.62 6.25-7.0
7.5-8.4 9.37-10.5 15.0-17.4 18.7-21.8 30.0-34.8 45.0-49.7 55.2-60.0 69.0-75.0
Remote Sensing
Possible
Remote ON/OFF Control
Possible
Parallel Operation
Possible
Series Operation
Possible
Monitoring Signal
PF(Open collector output)
Line DIP
Built to meet SEMI-F47 (200VAC Line only)
Other Function
PCB Coating on solder side and component side.
Environment
Operating Temperature
(*11)
℃
-10 to + 71, Guarantee Start up -40 to -10
-10 to +40
°
C
%
100
+50
°
C
%
83.9
100
+71
°
C
%
50
Storage Temperature
℃
-40 to +85
Operating Humidity
%
RH
10 - 90 (No Condensing)
Storage Humidity
%
RH
10 - 95 (No Condensing)
Vibration (*14)(*15)
At no operating, 10 - 55Hz (Sweep for 1min.) 19.6m/s² Constant, X,Y,Z 1hour each.
Designed to meet MIL-STD-810F 514.5 Category 4 figure 514.5C-1, category 10
Shock (In package)
(*15)
Less than 196.1m/s² Designed to meet MIL-STD-810F 516.5 Procedure I
Cooling
Forced Air By Blower Fan
Isolation
Withstand Voltage
Input - FG : 2kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG : 500VAC (300mA), (60V model 651VAC(390mA)), Output - CNT:100VAC (100mA) for 1min.
Isolation Resistance
More than 100M
Ω
Output - FG : 500VDC
More than 10M
Ω
Output - CNT : 100VDC at 25
℃
and 70%RH
Standards
Safety Standards
(*12)
Approved by
UL60950-1, CSA C22.2 No.60950-1, EN60950-1, EN50178. Built to meet DENAN.
PFHC
Built to meet IEC6100-3-2
EMI
Built to meet EN55011/EN55022-B, FCC-ClassB, VCCI-ClassB, CISPR-ClassB.
Immunity
Built to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3), -5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (max)
g
3200
Size (W
×
H
×
D)
mm
126.5 x 82 x 240 ( Refer to outline drawing )
(*1) At Ta=25
℃
and maximum output power.
(*2) For cases where conformance to various safety specs (UL, CSA,EN) are required, input voltage range will be 100 - 240VAC(50/60Hz).
(*3) First in-rush current. Not applicable to the first 0.2ms in-rush current flowing into the power supply noise filter.
(*4) Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz. (at 100uF electric capacitor and 0.47uF film capacitor on the test fixture board.)
(*5) 85 - 265VAC , constant load.
(*6) No load-Full load, constant input voltage.
(*7) Constant current limit with automatic recovery. Over current condition for more than 5 seconds will cause the out-
put to shutdown. Output current exceeding maximum rated output current for more than 10 seconds continuously
will result to output shutdown.
(*8) OVP circuit will shut down output, manual reset (Power cycle) or ON/OFF CNT signal reset.
(*9) At 100/200VAC, nominal output voltage and maximum output current.
(*10) Measured by the each measuring method of UL, CSA, EN and DENAN(at 60Hz), Ta=25
℃
.
(*11) Ratings - Derating at standard mounting.
- Load (%) is percent of maximum output power or maximum output current,whichever is greater.
- As for other mountings, refer to derating curve.
- For conditions of start up at -40
℃
to 10
℃
, refer to derating curve.
(*12) As for DENAN,built to meet at 100VAC.
(*13) Peak output current is less than 10 seconds, and duty 35% max.(200VAC Line only)
(*14) Category 4 exposure levels : Truck transportation over U.S. highways, Composite two-wheeled trailer.
(*15) It is compulsory to fix BRACKET onto product for MIL-STD-810F 516.5 Procedure
Ⅰ
and MIL-STD-810F 514.5 category 10 compliance.
Refer to mounting method.
HWS1000/HD Specifications
(Read instruction manual carefully, before using the power supply unit.)
Please refer to page 50 for MIL-STD Mounting
44
・All specifications are subject to change without notice.