(*1) ( ): Peak output current at 200VAC. Operaing time at peak output is less than 10sec, duty is less than 35%.
(*2) At 100/200VAC, Ta=25
℃
and maximum output power.
(*3) For cases where conformance to various safety specs (UL, CSA, EN) are required, to be described as 100 - 240VAC
(50/60Hz).
(*4) Not applicable for the in-rush current to noise filter for less than 0.2ms.
(*5) Measure with JEITA RC-9131A probe, bandwidth of scope :100MHz.
(*6) 85 - 265VAC, constant load.
(*7) No load-Full load, constant input voltage.
(*8) 3.3, 5V model: Constant current limit and hiccup with automatic recovery.
12 - 48V model: Constant current limit with automatic recovery.
Avoid to operate at over load or short circuit condition for more than 30 seconds.
(*9) OVP circuit will shut the output down, manual reset (CNT reset or re power on).
(*10) At 100/200VAC, nominal output voltage and maximum output current.
(*11) Measured by the each measuring method of UL, CSA, EN and DENAN (at 60Hz), Ta=25
℃
.
(*12) Ratings - Derating at standard mounting. Refer to output derating curve.
- Load (%) is percent of maximum output power or maximum output current, whichever is greater.
(*13) For -40
°
C to -10
°
C need 3minutes to stabilize the output voltage.
(*14) Category 4 exposure levels : Truck transportation over U.S. highways, composite two-wheeled trailer.
(*15) As for DENAN, designed to meet at 100VAC.
ITEMS/UNITS MODEL HWS300-3/HD
HWS300-5/HD
HWS300-12/HD
HWS300-15/HD
HWS300-24/HD
HWS300-48/HD
Input
Voltage Range
(*3)
V
AC85 - 265 or DC120 - 330
Frequency
(*3) Hz
47 - 63
Power Factor (100/200VAC)(typ) (*2)
0.99 / 0.95
Efficiency (100/200VAC)(typ) (*2)
%
74 / 77
79 / 82
80 / 83
82 / 85
Current (100/200VAC)(typ)
(*2)
A
2.7 / 1.4
3.8 / 1.9
4.1 / 2.1
Inrush Current (100/200VAC)(typ) (*4)
A
20 / 40
Leakage Current
(*11) mA
Less than 0.75. (0.2 (typ) at 100VAC / 0.44 (typ) at 230VAC)
Output
Nominal Voltage
VDC
3.3
5
12
15
24
48
Maximum Current
(*1)
A
60
27
22
14 (16.5)
7
Maximum Power
W
198
300
324
330
336
Maximum Line Regulation
(*6) mV
20
48
60
96
192
Maximum Load Regulation
(*7) mV
30
72
90
144
288
Temperature Coefficient
Less than 0.02% /
℃
Maximum Ripple & Noise (0<Ta<70
℃
) (*5) mVp-p
120
150
350
Maximum Ripple & Noise (
−
10<Ta< 0
℃
) (*5) mVp-p
180
200
400
Hold-up Time (typ)
(*10) ms
20
Voltage Adjustable Range
VDC
2.64-3.96
4.0-6.0
9.6-14.4
12.0-18.0
19.2-28.8
38.4-52.8
Function
Over Current Protection
(*8)
A
>63
>63
>28.4
>23.1
>16.7
>7.4
Over Voltage Protection
(*9) VDC
4.13-4.95
6.25-7.25
15.0-17.4
18.8-21.8
30.0-34.8
55.2-64.8
Remote Sensing
Possible
Remote ON/OFF Control
Possible
Parallel Operation
Possible
Series Operation
Possible
Monitoring Signal
PF (Open collector output)
Line DIP
Designed to meet SEMI-F47 (200VAC Line only)
Environment
Operating Temperature (*12)(*13)
℃
-10 to +71 (-10 to +50: 100%, +71: 50%)
Guarantee Start up at -40 to -10
Storage Temperature
℃
-40 to +85
Operating Humidity
%
RH
10 - 90 (No dewdrop)
Storage Humidity
%
RH
10 - 95 (No dewdrop)
Vibration (*14)
At no operating, 10 - 55Hz (sweep for 1min)
19.6m/s² constant, X, Y, Z 1hour each.
Designed to meet MIL-STD-810F 514.5 Category 4,10
Shock (In package)
Less than 196.1m/s²
Designed to meet MIL-STD-810F 516.5 Procedure I, VI
Cooling
Forced air by blower fan
Isolation
Withstand Voltage
Input - FG : 2.5kVAC (20mA), Input - Output : 3kVAC (20mA)
Output - FG: 500VAC (100mA), Output-CNT: 100VAC(100mA) for 1min
Isolation Resistance
More than 100M
Ω
Output - FG : 500VDC
More than 10M
Ω
Output -CNT : 100VDC at 25
℃
and 70%RH
Standards
Safety Standards
(*15)
Approved by UL60950-1, CSA C22.2 No.60950-1, EN60950-1, EN50178
Designed to meet DENAN
PFHC Designed
to
meet
IEC61000-3-2
EMI
Designed to meet EN55011/EN55022-B, FCC-B, VCCI-B
Immunity
Designed to meet IEC61000-4-2(Level 2,3), -3(Level 3), -4(Level 3),
-5(Level 3,4), -6(Level 3), -8(Level 4), -11
Mechanical
Weight (typ)
g
1000
Size (W x H x D)
mm
61 x 82 x 165 (Refer to outline drawing)
Please refer to "TDK-Lambda
EMC Filters" catalog.
●Recommended EMC Filter
RSEN-2006
HWS300/HD Specifications
(Read instruction manual carefully, before using the power supply unit.)
HWS
300/HD
40
・All specifications are subject to change without notice.
Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
Summary of Contents for HWS?HWS
Page 1: ...HWS Series AC DC Switching Power Supply HWS HWS ME HWS HD HWS P...
Page 30: ......
Page 68: ......