109
・All specifications are subject to change without notice.
Instruction Manual
HWS
HWS HD
HWS ME
HWS-P
Withstand Voltage
This series is designed to withstand 3.0kVAC between in-
put and output, 2.0kVAC between input and FG (chassis),
500VAC (60V model : 651VAC) between output and FG
(chassis), and 100VAC between output and CNT・PF termi-
nal each for 1 minute. When testing withstand voltage, set
current limit of withstand voltage test equipment at 20mA.
(Output-FG (chassis) : 300mA (60V model : 390mA), Out-
put- CNT・PF : 100mA).
The applied voltage must be gradually increased from zero
to testing value and then gradually decreased for shut
down. When timer is used, the power supply may be dam-
aged by high impulse voltage at timer switch on and off .
Connect input and output as follows. If output is left open
during test, output voltage might appear momentarily.
This product have monolithic ceramic capacitor in
secondary circuit to frame ground.
Some of the withstand voltage tester may generate high
voltage at the matching with monolithic ceramic capacitor
and may cause the unit damage.
So, please check the waveform of test voltage.
Output Voltage External Control (PV)
(A)Control by External Voltage
Output voltage external control function is provided.
Output voltage can be varied by applying an external
voltage (1−6V) to PV terminal and COM termi-
nal. Note if an external voltage is not applied, there
will be no output. Please consider the following char-
acteristics below when operating the unit.
Note: Only as for the model of 3V output, the output voltage
is used from 30% to 120% at the PV voltage is from
1.5V to 6.0V
Note: Only as for the model of 5-36V output, the output voltage
is used from 20% to 120% at the PV voltage is from 1V
to 6.0 V
Note: Only as for the model of 48V, 60V output, the
output voltage is used from 20% to 110% at the PV
voltage is from 1V to 5.5V
Note: Only as for the model of 48V, 60V output, the
maximum output voltage is used up to 110% at 90%
load current.
(B) Control by External Variable Resistor
PV terminal and COM terminal usage is the same
as explained in section 「control by external voltage」 .
But in this method voltage for control is supplied
through REF terminal. Variable resistor is connected
between REF terminal and COM terminal and the
middle point of variable resistor is connected to PV
terminal. Please use the output voltage within 20% -
120% of rated output voltage value (3V model : 30%
- 120 % , 48V, 60V model : 20 % - 110 % ). Wires
for control lines must be twisted wire or shield wire.
In addition, maximum variable voltage when control
by external variable resistor is rated output voltage
(100% ). When output voltage must be externally con-
trol to 120% of rated output voltage (110% for 48V,
60V model), please follow the following procedure.
(1) PV terminal and REF terminal is short by using
standard connector supplied.
(2) Set the power supply output voltage to maximum
value of the output voltage variable range mentioned
in specifi cation standard by adjusting V.ADJ volume
at the front panel.
(3) Remove standard connector after input is cut off .
(4) Connect external variable resistor (50kΩ) between
REF terminal and COM terminal. Then connect
middle point of external variable resistor to PV
terminal.(sensing current is 1.4mA)
When output voltage is over rated value, please make
sure that maximum output power is below rated value.
Moreover, when output voltage is below rated value,
please make sure that maximum output current is below
rated value.
Please consider the following characteristic during usage.
HWS
1500
+
S
-
S
Load
Power
supply
VR1
PV
REF
COM
+
-
Sensing current:1.4mA
Variable resistor 50kΩ
Connection method
PV Voltage (Nominal Input Voltage)
Output
+
S
-
S
Load
Power
Supply
1−6V
PV
COM
+
-
Nominal
Output
Voltage
Connection Method
Output Voltage Linearity
3−36V model
110%
120%
20%
30%
6V
5.5V
5V
1V 1.5V
0
48V、60V model
3V model
Output
Load Current
Operating Area
Nominal
Output
Voltage
Output Voltage Derating
110%
120%
20%
30%
0
83%90% 100%
48V、60V model
3V model
3−36V model
+
S
+
-
-
S
PC
CNT
TOG
PF
FG
AC
(L)
AC
(N)
+
S
+
-
-
S
PC
CNT
TOG
PF
FG
AC
(L)
AC
(N)
Output − FG (chassis)
500VAC 1min. (300mA)
(60V model : 651VAC 1min (390mA)
)
+
S
+
-
-
S
PC
CNT
TOG
PF
FG
AC
(L)
AC
(N)
Input − FG (chassis) (solid line)
2kVAC 1min. (20mA)
Input − Output (dotted line)
3kVAC 1min. (20mA)
Output − CNT・PF
100VAC 1min. (100mA)
Withstand
Voltage Tester
Withstand
Voltage Tester
Withstand
Voltage Tester