2800 Laura Lane Madison, WI 53562 | 800.288.9383 Fax: 608.836.9044 | www.tcsbasys.com
17
Information on the advanced status screen is broken into four groups:
•
Inputs
:
-
Type
: The programmed thermostat type (conventional or heat pump).
-
System
: The programed system mode.
-
Fan
: The active fan mode.
• Digital
Inputs
: The status of each Digital Input is shown with both an indicator light and text. Additionally, the
programmed mode of the Digital Input is shown next to the status text.
• Economizer
:
-
Enabled
: Indicates whether the economizer is currently allowed to modulate open. This depends on the occupancy
state, whether free cooling is available, and if cooling is needed.
-
Free Cooling
: Indicates when the economizer feature determines that free cooling is available. This depends on
the programed economizer mode. For example, in dry bulb setpoint mode, free cooling is indicated as available
when the outside air temperature is below the economizer drybulb setpoint.
-
Freeze Protect
: Indicates that the outside air damper is being modulated closed in order to protect equipment
from freezing.
• Analog Inputs & Outputs
: (model speci
fi
c)
-
Analog Inputs
: Two values are shown for each of the analog inputs. The value on the left shows the reading in
milliamps, while the value on the right shows the input scaled to engineering units.
-
Analog Outputs
: Two values are shown for each of the analog outputs. The value on the left shows the output in
milliamps, while the value on the right shows the output as a percent of full range. Additionally, the mode of the
analog output is shown next to the percentage.
4.2.3 Network Status
Figure 8
Information on the advanced status screen is broken into three groups:
• RS-485
Settings
:
-
Mode
: This indicates the programmed network mode.
-
Device ID
: The programmed device instance number.
-
Name
: The programed device name.
-
Address
: The programmed device address.
-
Baud Rate
: The programmed device baud rate.
• RS-485
Status
:
-
Link
: Indicates the overall status of the network connection. This consists of both an indicator light and associated
text. Touching the text brings up a dialog box with additional status information. The following states may be
shown:
USER