2800 Laur
a Lane ~ Madison, WI 53562 | 800.288.9383 ~ fax: 608.836.9044 | www
.tcsbasys.com
35
TM
Object
ID
Name
Description
Default V
alue
PV
Access
Object Pr
o
fi
le
Additional Info
4010
4020
4040
4050
MSV
-1102
Unoccupied F
an
Mode
Unoccupied F
an Mode
(1) A
ut
o
R/W (NVM)
Basic
(496-19-1)
States: (1) A
ut
o, (2)
On, (3) Cool, (4) A
ut
o
+ Re-cir
c
PIV
-1105
Fan P
ost-
Conditioning
Runtime for Heat
How long the fan runs after all heat stages
become inactiv
e
60 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 3600 sec
PIV
-1106
Fan P
ost-
Conditioning
Runtime for Cool
How long the fan runs after all cool stages
become inactiv
e
60 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 3600 sec
B
V
-1110
Fan Pr
oving
Input Status
Fan Pr
oving Input Status
R/W (RAM)
Commandable
(496-5-2)
States: (1) Activ
e, (0)
Inactiv
e
B
V
-1111
Fan Pr
oving
Failur
e Status
Indicates whether the fan has failed pr
oving.
W
rite t
o inactiv
e t
o r
eset
fan pr
oving
R/W (RAM)
Basic
(496-5-1)
States: (1) F
ailed, (0)
Ok
PIV
-1112
Fan Pr
oving
Dela
y
Dela
y after fan is
activ
ated befor
e pr
oving
is per
formed
30 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 600 sec
PIV
-1113
Fan Pr
oving
Reco
ve
ry
A
ttempts
Fan Pr
oving Reco
ve
ry
A
ttempts
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 10
PIV
-1114
Fan Pr
oving
Reco
ve
ry
Dela
y
Dela
y between each
reco
ve
ry
attempt after a
pr
oving failur
e
600 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 43200 sec
PIV
-1115
Fan Recir
c
P
eriod
P
eriod o
ver which
the r
ecir
culation is
calculated
20 min
R/W (NVM)
Basic
(496-48-1)
Range: 10 t
o 60 min
PIV
-1116
Fan Recir
c
Occupied Pe
rcentage
Minimum duty cy
cle for
fan r
ecir
culation when
occupied
5.00%
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 100 %
PIV
-1117
Fan Recir
c
Unoccupied P
er
centage
Minimum duty cy
cle for
fan r
ecir
culation when
unoccupied
0.00%
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 100 %
MSV
-1001
Thermostat T
ype
Thermostat T
ype
(1)
Conv
entional
R/W (NVM)
Basic
(496-19-1)
States: (1)
Conv
entional, (2)
Heat Pump
APPENDIX