P8510 intelligent thermometer 

 

P8511 intelligent single-channel transducer 

 

P8541 intelligent four-channel transducer 

USER MANUAL

Summary of Contents for P8510

Page 1: ...COMET SYSTEM www cometsystem cz P8510 intelligent thermometer P8511 intelligent single channel transducer P8541 intelligent four channel transducer USER MANUAL ...

Page 2: ...serves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not responsible for damages caused by using the device in conflict with this manual To damages caused by using the device in conflict with this manual can not be provide free repairs during the warranty period This user manual describes device with firmware version 4 5 5 x For device...

Page 3: ...otocols 20 Website 20 SMTP sending e mails 20 SNMP 21 Modbus TCP 22 SOAP 23 Syslog 24 SNTP 24 Troubleshooting 25 I forgot the device IP address 25 I can not connect to the device 25 Error or n a is displayed instead the measured value 26 Error2 is displayed on all channels instead the measured value 26 I forgot the password for setup 26 Factory defaults 26 Technical specifications 27 Dimensions 27...

Page 4: ... person The device contains no serviceable parts inside standard means Don t use the device if it doesn t work correctly If you think that the device is not working correctly let check it by qualified service person It s forbidden to use the device without the cover Inside the device can be a dangerous voltage and may be risk of electric shock Use only the appropriate power supply adapter accordin...

Page 5: ...or web interface TSensor software can be free downloaded from the manufacturer s website Also you will find there latest firmware for your device Do not upload to your device firmware which is not designed for it Unsupported firmware can damage your device Device does not support powering over Ethernet cable PoE PoE splitter must be used Compatible PoE splitter can be purchased as optional accesso...

Page 6: ...P8541 Transducer up to 4 temperatures probes type DSTR162 C DSTGL40 C DSTG8 C or relative humidity probe DSRH Mounting the device check if the equipments from previous chapter are available install the latest version of TSensor software This software is used to all device settings TSensor software can be free downloaded from the manufacturer s website Software can be also supplied on CD Device con...

Page 7: ... address must be changed according to informations from the previous point When you installing several new devices connect them to the network one after another connect probes to P8511 or P8541 Transducer connect the Ethernet connector connect the power adapter 5V 250mA LEDs on LAN connector should blink after connecting the power P8510 Thermometer connection P8511 Transducer connection ...

Page 8: ...sducer connection Connect via PoE splitter Device settings run configuration software TSensor on your PC switch to an Ethernet communication interface press button Find device the window shows all available devices on your network ...

Page 9: ...is already used the device will not work correctly and there will be collisions on the network If the device detects a collision of IP address then reboot is performed automatically after changing IP address device is restarted and new IP address is assigned Restart of the device takes about 10 seconds connect to device using TSensor software and check the measured values If P8511 or P8541 Transdu...

Page 10: ...the default IP address was not changed then insert http 192 168 1 213 Displayed web page lists actual measured values If the web pages are disabled you can see text Access denied If the measured value exceeds the measurement range or probe is not correctly installed then is shown Error message If the channel is switched off the web site displayed n a instead of the value ...

Page 11: ... can be setup using web interface or TSensor software Web interface can be managed by the web browser Main page will be shown when you insert device address into address bar of your web browser There you find actual measured values Page with history graphs is shown when you click to tile with actual values Access to device setup is possible via tile Settings Chapter 3 ...

Page 12: ... can be obtain automatically from DHCP server using option Obtain an IP address automatically Static IP address is configurable via field IP address It is not necessary setup Default gateway while you use device inside one subnet only Option Standard subnet mask sets network mask automatically according A B or C network class Subnet mask field must be set manually when network with non standard ra...

Page 13: ...larm was not set In Point 3 the temperature has risen over limit again During the time delay the value does not drop below the set limit and therefore was in Point 4 caused alarm At this moment were sent e mails traps and set alarm flag on website SNMP and Modbus The alarm lasted up to Point 5 when the temperature dropped below the set hysteresis temperature limit hysteresis At this moment was act...

Page 14: ...confirmed using Apply settings button History values are cleared after changing of channel settings SOAP protocol SOAP protocol can be enabled by option SOAP protocol enabled IP address of the destination http server is configurable via SOAP server IP address filed For setup of destination server port can be used option SOAP server port Target place of the http server can be set via SOAP server ta...

Page 15: ...Into fields Recipient 1 to Recipient 3 it is possible set address of email recipients Option Short email enable sending emails in short format This format is usable when you need to forward emails into SMS messages When option Alarm email repeat sending interval is enabled and there is active alarm on channel then emails with actual values are sent repeatedly Info email sending interval option ena...

Page 16: ... Modbus port field Syslog protocol can be enabled using item Syslog enabled Syslog messages are sent to IP address of the Syslog server field Syslog server IP address SNMP For reading values via SNMP it is necessary to know password SNMP read community SNMP Trap can be delivered up to three IP address IP address of the Trap recipient SNMP Traps are sent at alarm or error state on the channel Trap ...

Page 17: ...nchronization every hour decrease this synchronization interval to one hour WWW and security Security features can be enabled by the Security enabled option When security is enabled it is necessary to set administrator password This password will be required for device settings When secured access is required even to actual values reading it is possible to enable User account only for viewing Port...

Page 18: ...aults button set the device into factory configuration Network parameters IP address Subnet mask Gateway are left without changes Network parameters are changed while you close jumper inside the device After jumper closing it is necessary connect power supply Factory defaults have no effect to user correction inside probe Factory parameters settings Parameter Value IP address of SMTP server 0 0 0 ...

Page 19: ...e cleared SOAP sending interval sec 60 SOAP protocol enabled off Syslog server IP address 0 0 0 0 Syslog protocol enabled off SNTP server IP address 217 31 205 226 GMT offset min 0 NTP synchronization every hour off SNTP synchronization enabled off MTU 1400 Periodic restart interval off Demo mode off Turn on all channels yes Upper limit 50 Lower limit 0 Hysteresis hysteresis for alarm clearing 1 D...

Page 20: ...ry can be exported in CSV format History storage interval can be set using TSensor software or web interface History is erased after every reboot of the device Reboot of the device is performed when the power supply is disconnected and also after configuration change The device allows you to customize the design of web pages Details of how to change the design you can find in the manual appendix M...

Page 21: ... 3 6 1 4 1 22626 1 5 2 ch 5 High limit Int 10 1 3 6 1 4 1 22626 1 5 2 ch 6 Low limit Int 10 1 3 6 1 4 1 22626 1 5 2 ch 7 Hysteresis Int 10 1 3 6 1 4 1 22626 1 5 2 ch 8 Delay Integer 1 3 6 1 4 1 22626 1 5 2 ch 9 Unit String 1 3 6 1 4 1 22626 1 5 2 ch 10 Alarm on channel text String 1 3 6 1 4 1 22626 1 5 3 1 0 SNMP Trap text String 1 3 6 1 4 1 22626 1 5 4 1 1 ch nr History table value String When al...

Page 22: ...serial number BCD 39974 0x9C26 Device type uInt 39975 39978 0x9C27 0x09C2A Actual measured value on channel Int 10 39980 39983 0x9C2C 0x9C2F Unit on the channel Ascii 39985 39988 0x9C31 0x9C34 Channel alarm state uInt 39990 39999 0x9C36 0x9C3F Unused n a 40000 0x9C40 Channel 1 temperature Int 10 40001 0x9C41 Channel 1 alarm status Ascii 40002 0x9C42 Channel 1 upper limit Int 10 40003 0x9C43 Channe...

Page 23: ...e side Due to it is not necessary use port forwarding If the SOAP message can not be delivered warning message via SNMP Trap or Syslog protocol is sent The file with the XSD schema can be downloaded from http cometsystem cz schemas soapP8xxx xsd SOAP message example Host 192 168 001 132 Content Type text xml charset utf 8 Content Length 751 SOAPAction http tempuri org InsertP8xxxSample xml version...

Page 24: ...e error Email socket error SOAP file not found SOAP message sending error SOAP host error SOAP sock error SOAP delivery error High alarm CHx Upper alarm on channel Low alarm CHx Lower alarm on channel Clearing CHx Clearing alarm on channel Error CHx Measuring error SNTP The device allows time synchronization with NTP SNTP server SNMP protocol version 3 0 is supported RFC1305 Time synchronization i...

Page 25: ...her network Select the window Find device in TSensor software and press Change IP address Follow the software instructions To assign IP address automatically using DHCP server set the device IP address to 0 0 0 0 Device IP address is not displayed in window Find device In TSensor software menu press Help My device was not found in window Find device Follow the software instructions MAC address of ...

Page 26: ...layed on all channels instead the measured value Error2 indicates short circuit of measurement bus Check if correct probes are connected Probes Pt100 Pt1000 Ni100 Ni1000 can not be used with this device Make sure that cables of probes are not damaged I forgot the password for setup Please reset device to factory defaults Procedure is described at following point Factory defaults This procedure res...

Page 27: ...IE SNC P85x1 11 27 Technical specifications Informations about technical specifications of the device Dimensions P8510 Thermometer P8511 Transducer Chapter 6 ...

Page 28: ...8 C in temperature range from 10 C to 80 C 2 0 C in temperature range from 10 C to 30 C Accuracy P8511 P8541 depending on used probe e g probe DSTR162 C parameters 0 5 C in temperature range from 10 C to 80 C 2 0 C in temperature range from 10 C td 30 C Resolution 0 1 C 0 1 RH P8510 temperature measurement range 30 C to 80 C P8511 and P8541 temperature measurement range limited by range of used pr...

Page 29: ...sers Internet Explorer 9 Mozilla Firefox 12 and later Google Chrome 18 and later Opera 11 and later Safari 5 and later Device should be also compatible with other browsers Functionality wasn t tested with other web browsers Recommended minimum screen resolution 1024 x 768 Memory 1000 values for each channel inside non backup RAM memory Case material ABS Mounting the device With two holes at the bo...

Page 30: ...CK 19 with universal holder MP046 accessories then sensor cover can be placed horizontally P8511and P8541 working position arbitrary End of operation Disconnect the device and dispose it according to current legislation for dealing with electronic equipment Electronic devices must be professionally destroyed in accordance with EU Directive 2002 96 ES of 27th January 2003 Technical support and serv...

Page 31: ...e 17240 Guaranteed watertight IP67 sensor connected to PVC cable with lengths 1 2 5 or 10m Temperature probe DSTG8 C Temperature probe 50 to 80 C with a digital sensor DS18B20 and with Cinch connector for P8511 and P8541 Transducer Maximum temperature of the probe is 125 C Probe accuracy 0 5 C from 10 to 80 C else 2 C Steal steel case with length 40mm diameter 5 7mm Stainless steel type 17240 Guar...

Page 32: ...er for RACK 19 MP047 Universal holder for easy mounting probes in RACK 19 Database software DBS Sensor monitor Database software DBS Sensor Monitor for online data collection and data analysis from Ethernet sensors It contains all components for data acquisition from sensors including a one license of DBV Database Viewer For more information please visit our webpage ...