IE-SNC-P85x1-11
30
Operating terms
Temperature and humidity range in case with electronic:
-30°C to +80°C, 0 to 100%RH (no condensation)
Temperature range of recommended probe DSTR162/C for P8511 and P8541:
-30°C to +80°C
Temperature range of probe DSTGL40/C for P8511 and P8541:
-30°C to +80°C
Temperature range of probe DSTG8/C for P8511 and P8541:
-50°C to +80°C
Temperature and humidity range of probe DSRH for P8511 and P8541:
0°C to +50°C, 10 to 90%RH
P8510 working position:
with sensor cover downwards. When mounting in RACK 19" with
universal holder MP046 (accessories) then sensor cover can be
placed horizontally.
P8511and P8541 working position:
arbitrary
End of operation
Disconnect the device and dispose it according to current legislation for
dealing with electronic equipment. Electronic devices must be professionally
destroyed in accordance with EU Directive 2002/96/ES of 27th January 2003.
Technical support and service
Technical support and service is provided by distributor. Contact is included in warranty
certificate.
Preventive maintenance
Make sure the cables and probes are not damaged periodically. Recommended calibration
interval is 2 years. Recommended calibration interval for device with humidity probe
DSRH is 1 year.