![Comet System P8510 User Manual Download Page 23](http://html1.mh-extra.com/html/comet-system/p8510/p8510_user-manual_2640774023.webp)
IE-SNC-P85x1-11
23
40022
0x9C56
Channel 4 hysteresis
Int*10
40023
0x9C57
Channel 4 delay
uInt
Description:
Int*10
registry is in format integer*10 – 16 bits
uInt
registry range is 0-65535
Ascii
character
BCD
registry is coded as BCD
n/a
item is not defined, should be read
Possible alarm states:
no
no alarm
lo
value is lower than set limit
hi
value is higher than set limit
SOAP
The device allows you to send currently measured values via
SOAP v1.1
protocol. The
device sends values in XML format to the web server. The advantage of this protocol is
that communication is initialized by the device side. Due to it is not necessary use port
forwarding. If the SOAP message can not be delivered, warning message via SNMP Trap
or Syslog protocol is sent. The file with the XSD schema can be downloaded from:
http://cometsystem.cz/schemas/soapP8xxx.xsd. SOAP message example:
Host: 192.168.001.132
Content-Type: text/xml; charset=utf-8
Content-Length: 751
SOAPAction: "http://tempuri.org/InsertP8xxxSample"
<?xml version="1.0" encoding="utf-8"?>
<soap:Envelope xmlns:soap="http://schemas.xmlsoap.org/soap/envelope/"
xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance"
xmlns:xsd="http://www.w3.org/2001/XMLSchema">
<soap:Body>
<InsertP8xxxSample xmlns="http://cometsystem.cz/schemas/soapP8xxx.xsd">
<name>
Ethernet Transducer
</name>
<sn>
11940986
</sn>
<tmr>
60
</tmr>
<kind>
4353
</kind>
<c1>
<v>
26.3
</v>
<u>
C
</u>
<a>
no
</a>
<e>
1
</e>
</c1>
...
...
...
<c5>
<v>
-11000
</v>
<u>
n/a
</u>
<a>
no
</a>
<e>
0
</e>