2800 Laur
a Lane ~ Madison, WI 53562 | 800.288.9383 ~ fax: 608.836.9044 | www
.tcsbasys.com
49
TM
Object
ID
Name
Description
Default V
alue
PV
Access
Object Pr
o
fi
le
Additional Info
4010
4020
4040
4050
A
V
-1802
Residential
Mode Hold Heat
Setpoint
Residential Mode Hold
Heat Setpoint
70 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
A
V
-1803
Residential
Mode Hold Cool
Setpoint
Residential Mode Hold
Cool Setpoint
75 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
PIV
-501
User Access
Code
Access code r
equir
ed
to
change settings at
thermostat. Set t
o 0 t
o
disable
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 9999
MSV
-502
Displa
y Clock
Format (12/24
hour)
Time format shown on
local displa
y
(1) 12 Hour
R/W (NVM)
Basic
(496-19-1)
States: (1) 12 Hour
, (2)
24 Hour
MSV
-503
Displa
y Units
(F/C
)
Temper
atur
e units on
local displa
y
(1)
Fahr
enheit
R/W (NVM)
Basic
(496-19-1)
States: (1) F
ahr
enheit,
(2) Celsius
MSV
-504
Displa
y
Brightness
Backlight brightness on
local displa
y
(3) High
R/W (NVM)
Basic
(496-19-1)
States: (1) Low
, (2)
Medium, (3) High
MSV
-505
Displa
y Banner
Mode
Information shown in top-right corner of local
displa
y
(1) Date & Time and
Name
R/W (NVM)
Basic
(496-19-1)
States: (1) Date & Time and Name, (2) Date &
Time Only
CSV
-506
Displa
y Info
Text
Optional text shown
on local displa
y.
A
ut
omatically clear
ed
after Command
Timeout
R/W (RAM)
Basic
(496-40-1)
FILE-1300
Firmwar
e
Upgr
ade File
Firmwar
e Upgr
ade File
Data
fl
ash
(496-10-1)
FILE-1301
Fact
or
y Settings File
Fact
or
y Settings File
Con
fi
gur
ation
(496-10-2)
FILE-1302
User Settings
File
User settings for backup
and r
est
or
e
Con
fi
gur
ation
(496-10-2)
FILE-1303
Oper
ation
Statistics File
Oper
ation Statistics File
Con
fi
gur
ation
(496-10-2)
FILE-1320
Diagnostic Log
File
Diagnostic Log File
Basic
(496-10-3)
APPENDIX