Object
ID
Name
Description
Default V
alue
PV
Access
Object Pr
o
fi
le
Additional Info
4010
4020
4040
4050
B
V
-1541
O
A
Damper
Dischar
ge Air LL
Enable
O
A
Damper Dischar
ge
Air Low Limit Enable
(1) Enabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1542
O
A
Damper
Dischar
ge Air LL
Setpoint
Setpoint at which the O
A
damper is fully closed
40 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
A
V
-1550
Pr
e-occ Pur
ge
Output
Pr
e-occupancy Pur
ge
Output
R (RAM)
Basic
(496-2-1)
Range: 0 t
o 100 %
B
V
-1551
Pr
e-occ Pur
ge
Enable
Pr
e-occupancy Pur
ge
Enable
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1552
Pr
e-occ Pur
ge
O
A
Damper
P
osition
Pr
e-occupancy Pur
ge
O
A
Damper P
osition
25.00%
R/W (NVM)
Basic
(496-2-1)
Range: 0 t
o 100 %
PIV
-1553
Pr
e-occ Pur
ge
Dur
ation
Dur
ation prior t
o
occupied occupancy state when f
eatur
e is
activ
e
60 min
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 240 min
A
V
-1700
Midpoint Bias
P
er
cent of output
allocated t
o heating for
midpoint contr
ol.
50.00%
R/W (NVM)
Basic
(496-2-1)
Range: 0 t
o 100 %
BSV
-1120
Limit and
Lockout Status
Limit and Lockout
Status
R (RAM)
Basic
(496-39-1)
Bits: (1) O
A
Lockout
Heat, (2) O
A
Lockout Cool, (3) DA
Limit Heat, (4)
D
A
Limit Cool, (5) LL
Changeo
ve
r
B
V
-1130
Outdoor Air
Lockout Enable
Outdoor Air Lockout
Enable
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1132
Outdoor Air Lockout Cool
Setpoint
Mechanical cooling is not allowed when
outdoor air is below this
value
55 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
A
V
-1131
Outdoor Air Lockout Heat
Setpoint
Heating is not allowed
when outdoor air is
abo
ve
this v
alue
70 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
APPENDIX
A