2800 Laur
a Lane ~ Madison, WI 53562 | 800.288.9383 ~ fax: 608.836.9044 | www
.tcsbasys.com
47
TM
Object
ID
Name
Description
Default V
alue
PV
Access
Object Pr
o
fi
le
Additional Info
4010
4020
4040
4050
B
V
-1140
Dischar
ge Air
Limit Enable
Dischar
ge Air Limit
Enable
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1142
Dischar
ge Air
Limit Cool Setpoint
Cooling is not allowed when dischar
ge air is
below this v
alue
40 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
A
V
-1141
Dischar
ge Air
Limit Heat Setpoint
Heating is not allowed when dischar
ge air is
abo
ve
this v
alue
140 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
B
V
-1150
Low Limit Changeo
ver
Enable
Outdoor air low limit
changeo
ver enable (heat
pump only)
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1151
Low Limit Changeo
ver
Setpoint
Compr
essors ar
e
disabled below this outdoor air setpoint (heat pump only)
20 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
B
V
-1250
DI Setpoint
Setback State
DI Setpoint Setback
State
R/W (RAM)
Commandable
(496-5-2)
States: (1) Activ
e, (0)
Inactiv
e
B
V
-1251
DI Setpoint
Setback Input
DI Setpoint Setback
Input
R/W (RAM)
Commandable
(496-5-2)
States: (1) Activ
e, (0)
Inactiv
e
PIV
-1252
DI Setpoint Setback Star
t
Dela
y
Dur
ation setback input
must r
emain activ
e
befor
e setback state
becomes activ
e
60 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 3600 sec
PIV
-1253
DI Setpoint
Setback
Minimum On
Time
DI Setpoint Setback Minimum On
Time
60 sec
R/W (NVM)
Basic
(496-48-1)
Range: 0 t
o 3600 sec
A
V
-1254
DI Setpoint
Setback V
alue
Amount t
o setback the
heating and cooling
setpoints
2 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -25 t
o 25 Deg F
APPENDIX
A