2800 Laur
a Lane ~ Madison, WI 53562 | 800.288.9383 ~ fax: 608.836.9044 | www
.tcsbasys.com
45
TM
Object
ID
Name
Description
Default V
alue
PV
Access
Object Pr
o
fi
le
Additional Info
4010
4020
4040
4050
A
V
-1514
Economiz
er O
A
Dr
ybulb Setpoint
Economiz
er Outdoor
Dr
ybulb Setpoint
60 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: -40 t
o 160 Deg
F
A
V
-1515
Economiz
er O
A
Dr
ybulb Compar
e
Delta
Diff
er
ence between
outdoor and space temper
atur
e befor
e
economiz
er is activ
ated
10 Deg F
R/W (NVM)
Basic
(496-2-1)
Range: 0 t
o 50 Deg F
B
V
-1516
Economiz
er
Unoccupied
Enable
Economiz
er Unoccupied Enable
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
B
V
-1517
Economiz
er DI
Enable
Economiz
er enable for
Digital Input economiz
er
mode
R/W (RAM)
Commandable
(496-5-2)
States: (1) Enabled,
(0) Disabled
B
V
-1518
Economiz
er F
ree
Cooling A
vailable
Indicates economiz
er
can pr
ovide cooling
R (RAM)
Basic
(496-5-1)
States: (1)
True, (0)
False
B
V
-1519
Economiz
er
Enabled
Indicates economiz
er
is curr
ently pr
oviding
cooling
R (RAM)
Basic
(496-5-1)
States: (1)
True, (0)
False
A
V
-1530
Demand Ventilation
Output
Demand V
entilation
Output
R (RAM)
Basic
(496-2-1)
Range: 0 t
o 100 %
B
V
-1531
Demand Ventilation
Enable
Demand V
entilation
Enable
(0) Disabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1532
Demand Ventilation Setpoint
Demand v
entilation CO2
setpoint
900 ppm
R/W (NVM)
Basic
(496-2-1)
Range: 0 t
o 1000 ppm
A
V
-1533
Demand
V
entilation Pr
op
Band
Demand v
entilation CO2
pr
opor
tional band
200 ppm
R/W (NVM)
Basic
(496-2-1)
Range: 0 t
o 1000 ppm
B
V
-1534
Demand
V
entilation LL
Ov
erride Enable
Allows demand
ventilation t
o o
verride
dischar
ge air low limit
(1) Enabled
R/W (NVM)
Basic
(496-5-1)
States: (1) Enabled,
(0) Disabled
A
V
-1540
O
A
Damper
Dischar
ge Air LL
Output
O
A
Damper Dischar
ge
Air Low Limit Output
R (RAM)
Basic
(496-2-1)
Range: 0 t
o 100 %
APPENDIX
A