Turn on the storage shelf first, and let it initialize. If you have two storage
shelves, turn on the storage shelf that is not connected to the appliance. When
that storage shelf has initialized turn on the other storage shelf and let it
initialize.
■
Turn on the appliance.
■
Ensure that the devices operate properly and begin the configuration for the
device.
Environmental specifications
Table 3-1
Environmental requirements
Requirement
Component
100VAC (U.S.)
Storage shelf nominal voltage
10°C to 35°C (50°F to 95°F)
Operating temperature
-10°C to 50°C (14°F to 122°F)
Storage temperature
-40°C to 60°C (-40°F to 140°F)
Transportation temperature
10% to 80%
Relative humidity operating range
10% to 90%
Relative humidity storage range
5% to 90%
Relative humidity transportation range
10°C (50°F) per hour maximum
Relative humidity operating gradient
15°C (59°F) per hour maximum
Relative humidity storage gradient
-30 meters to 3,000 meters (-98.4 FT to 9842.5
FT)
In altitudes from -60 meters to +1,800 meters,
the ambient temperature ranges from 5°C to
35°C.
When the altitude ranges from 1,800 meters to
3,000 meters, the environment temperature
decreases by 0.6°C if the altitude increases by
100 meters.
Operating altitude
-30 meters to 3,000 meters
Storage altitude
25
Preparing for hardware installation
Environmental specifications
Summary of Contents for NetBackup 5230
Page 1: ...Symantec NetBackup 5230 Appliance Hardware Installation Guide Release 2 6 1 2 21350324 ...
Page 16: ...Introduction Product documentation 16 ...
Page 22: ...Installation requirements Prerequisites for IPMI configuration 22 ...
Page 28: ...Preparing for hardware installation Checking the shipping packages 28 ...
Page 60: ...V validation appliance 44 NetBackup 5230 hardware checks 43 storage shelf 44 Index 60 ...