To install the Symantec Storage Shelf guide rails
1
Determine the installation positions of the guide rails in the rack.
This list describes the components in the diagram.
Description
Number
Location of a screw on the rear of the storage shelf handle. Insert
the screw here to connect the bottom of the rail to the rack. The
shelf sits on the ledge of the rail.
1
Location of a second screw to hold the storage shelf to the rack.
2
2
Locate the left mounting rail in the box in which the Symantec Storage Shelf
is shipped. The mounting plate at the front end of the rail is marked Front
Left.
3
Install snap-in cage nuts in the rack as follows:
■
Locate the M5 snap-in cage nuts in the package in which the storage shelf
was sent.
■
Identify the bottom third of the 3U section in the front and back of the
rack where you want to install the storage shelf.
Note:
The mounting rails are 1U high. The holes that are used to secure
the rail in the rack are in the middle of that height.
■
From the inside of the rack, insert snap-in cage nuts in cutouts in the front
and back where you want to install the mounting rail. Make sure that the
nuts are installed at the same level.
4
Orient the left mounting rail so that the lip is at the bottom and on the inside
of the rack. You can adjust the length of the rail to fit the depth of the rack.
Note:
The lip on the rail that supports the storage shelf must be on the inside
of the rack and at the bottom of the rail.
Installing hardware into racks
Installing the Symantec Storage Shelf guide rails
32
Summary of Contents for NetBackup 5230
Page 1: ...Symantec NetBackup 5230 Appliance Hardware Installation Guide Release 2 6 1 2 21350324 ...
Page 16: ...Introduction Product documentation 16 ...
Page 22: ...Installation requirements Prerequisites for IPMI configuration 22 ...
Page 28: ...Preparing for hardware installation Checking the shipping packages 28 ...
Page 60: ...V validation appliance 44 NetBackup 5230 hardware checks 43 storage shelf 44 Index 60 ...