To keep a convective air flow between the cabinet and the equipment room,
ensure there are no obstructions on all sides of the cabinet.
The applince takes in air from the front panel and circulates the air through the
system. Fans discharge air from the rear of the appliance. Air flows from front to
rear. The optional bezel can be installed on the front panel without any reduction
in air movement.
Environmental checklist
The following table describes the environmental checklist that must be completed
before appliance installation.
Table 2-2
Environmental considerations
Requirement
Item
The floor meets load-bearing requirements. Wiring troughs,
ladders, and holes are ready. All construction is complete.
Facility preparation
If the temperature in the room may exceed 35°C, install air
conditioners which can be restarted upon recovery from a
power failure. Do not let the air conditioner blow directly on
the devices.
Air conditioning
If the relative humidity is greater than 70%, a dehumidifying
device must be installed. Examples of such devices include an
air conditioner that provides a dehumidification function or
a special-purpose dehumidifier. Water penetration, dripping,
and condensation must all be prevented in the equipment
room.
Moisture proofing
If the temperature in the room is lower than the stated
minimum of 10°C, heating devices are required.
Heating
If the equipment room is located near a potential source of
dust or other particulate matter, a double aluminum alloy
window and an anti-theft fire door must be installed. The
devices must be separated from the door and a baffle must be
used to prevent dust pollution.
Dust proof
The equipment room must have a lightning protection device
such as lightning rod or lightning strip. The grounding of the
lightning protection device and the protective grounding of
the equipment room must share a grounding body.
Lightning strike protection
In addition, make sure that the following special requirements are met:
19
Installation requirements
Environmental checklist
Summary of Contents for NetBackup 5230
Page 1: ...Symantec NetBackup 5230 Appliance Hardware Installation Guide Release 2 6 1 2 21350324 ...
Page 16: ...Introduction Product documentation 16 ...
Page 22: ...Installation requirements Prerequisites for IPMI configuration 22 ...
Page 28: ...Preparing for hardware installation Checking the shipping packages 28 ...
Page 60: ...V validation appliance 44 NetBackup 5230 hardware checks 43 storage shelf 44 Index 60 ...