Sutron Corporation X-Link Operations & Maintenance Manual, Rev 1.63 5/24/2016 pg. 134
14.9.
Examples
Following is the captured communication of a user setting up measurement one
for a battery voltage measurement, making a measurement, and turning
recording on.
>M1 ACTIVE = 1
Setup changed
Active = On, Range (0=Off, 1=On)
>M1
Measurement M1 STAGE
Active = On
Label = STAGE
Right Digits = 3
Meas Interval = 00:00:05
Meas Time = 00:00:00
Averaging Time = 00:00:00
Logging Interval = 00:00:00
Log Error Value = -99999.00
Meas Type = SDI-12
SDI-12 Address = 0
SDI-12 Command = M!
SDI-12 Param = 1
Slope = 1.001000
Offset = 0.001000
Use Equation = Off
Alarm 1 Type = High
Alarm 1 Threshold = 10.000000
Alarm 2 Type = Off
Alarm 3 Type = Off
Alarm Tx Mode = Tx In Only
Alarm Deadband = 0.000000
Alarm Logging = Every Reading
Tx Data Content = Last
Measurement M1 STAGE reading
10.161
2012/03/30 12:08:05
In Alarm
>M1 RIGHT DIGITS = 2
Setup changed
Right Digits = 2 , Range (0, 7)
>M1 MEAS
Calculating...
Measurement M1 STAGE reading
10.16
2012/03/30 12:08:27
In Alarm
>RECORDING = 0