DO terminal (fault output dry contact):
the relay can be set to fault alarm output, and user
can configure it to be a normal open contact (COM
&
NO) or a normal close contact (COM
&
NC).
The relay is initially at the NC terminal, and it will trip to another contact when a fault occurs.
Use LED indicators or other equipment to indicate whether the inverter is in the faulty state.
figure 5-8
Normal open contact
figure 5-9
Normal close contact
Devices connected to the relay should comply with related requirements:
AC-Side Requirements
DC-Side Requirements
Max. voltage: 230 Vac
Max. current: 3A
Max. voltage: 30Vdc
Max. current: 3A
5.10.3 Connection Procedure
step 1 Unscrew the swivel nut from the communication terminal and take out the seal.