105
To prevent misuse or accidents caused by unrelated personnel: Post prominent
warning signs or demarcate safety warning areas around the inverter to prevent
accidents caused by misuse.
Restart the inverter only after removing the fault that impairs safety performance.
As the inverter contains no component parts that can be maintained, never open
the enclosure, or replace any internal components.
To avoid the risk of electric shock, do not perform any other maintenance opera-
tions beyond this manual. If necessary, contact SUNGROW for maintenance. Oth-
erwise, the losses caused is not covered by the warranty.
Touching the PCB or other static sensitive components may cause damage to the
device.
•
Do not touch the circuit board unnecessarily.
•
Observe the regulations to protect against electrostatic and wear an anti-static
wrist strap.
8.2.2 Disconnecting the Inverter
Danger of burns!
Even if the inverter is shut down, it may still be hot and cause burns. Wear protec-
tive gloves before operating the inverter after it cools down.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources. Lethal
voltages or damage to the inverter will follow if otherwise.
step 1 Disconnect the external AC circuit breaker and secure it against reconnection.
step 2 Rotate the DC switch to the "OFF" position for disconnecting all of the PV string inputs.
step 3 Wait about 25 minutes until the capacitors inside the inverter completely discharge.
step 4 Ensure that the DC cable is current-free via a current clamp.
- - End