39
(A) PV string
(B) Inverter
(C) Tracking control box
(D) Grid
(E) Monitoring device
(F) AC circuit breaker
Note: S is the cross-sectional area of the AC cable, and Sp is the cross-sectional area of the
grounding cable.
table 5-1 Cable Requirements
No.
Cable
Type
Specification
Cable Diameter
(mm)
Cross-sectional
Area(mm
2
)
1
DC cable
PV cable complying with
1,500V standard
4.7 ~ 6.4
4 ~ 6
2
Tracking
system
power
cable
Outdoor double-core copper
wire cable
8 ~ 18
0.5 ~ 10 (Recom-
mended 4 ~ 6)
3
External
ground-
ing cable
Outdoor single-core copper
wire cable
/
S
p
≥ S/2
4
AC cable
One Wire per Phase with
Multi-core Cable
refer to
ments(One Wire per Phase with Multi-
Two Wires per Phase with
Multi-core Cable
refer to
ments(Two Wires per Phase with Mul-
5
Commu-
nication
cable
Shielded twisted pair
4 ~ 11
0.2 ~ 1.3
The AC cable sealing plate delivered with the inverter varies. The actual product received
shall prevail.
The sealing plate and the required AC cables are as follows.