Fans inside the inverter are used to cool the inverter during operation. If the fans do not op-
erate normally, the inverter may not be cooled down and inverter efficiency may decrease.
Therefore, it is necessary to clean dirty fans and replace the broken fans in a timely manner.
The operation procedure is as follows:
step 1 Stop the inverter (see
8.2.2 Disconnecting the Inverter
).
step 2 Loosen the screw on the sealing plate of the fan module.
step 3 Press the tab of the latch hook, unplug the cable connection joint outwards, and loosen the
screw on the fan holder.
step 4 Loosen screws on the sides of fans.
User Manual