44
step 2 Remove the screw on the grounding terminal and fasten the cable with a screwdriver.
step 3 Apply paint to the grounding terminal to ensure corrosion resistance.
The grounding screws have been anchored to the side of the inverter before deliv-
ery, and do not need to be prepared.
There are two grounding terminals. Use one of them to ground the inverter.
- - End
5.6
AC Cable Connection
5.6.1 AC Side Requirements
Only with the permission of the local grid department, the inverter can be con-
nected to the grid.
Before connecting the inverter to the grid, ensure the grid voltage and frequency comply with
requirements, for which, refer to
"Technical Data"
. Otherwise, contact the electric power
company for help.
AC Circuit Breaker
Over-current protection devices, such as AC circuit breakers and fuses, must be
installed on the AC side of the inverter and the grid side to ensure safe disconnec-
tion between the inverter and the grid.
•
Do not connect any local load between the inverter and the AC circuit breaker
except for the tracking axis.
•
Multiple inverters cannot share one AC circuit breaker.