2-10
Netra CP3260 Blade Server User’s Guide • April 2009
2.5.1.1
To Remove FB-DIMM Memory Modules
You might need to remove a FB-DIMM module from the Netra CP3260 blade server
if you are returning the FB-DIMM module or the blade server for service, or if you
are replacing a module with another FB-DIMM module.
Note –
Safely store the original factory-shipped FB-DIMM and related FB-DIMM
packaging. You might wish to store any removed FB-DIMM in the new FB-DIMM
packaging, or use the packaging for service.
To remove a FB-DIMM from the Netra CP3260 blade server, perform the following
steps:
1. Take antistatic precautions: attach and electrically ground the wrist strap.
Caution –
Always wear a grounded antistatic wrist strap when handling modules.
2. Place the Netra CP3260 blade server on an antistatic mat, or on the blade
server’s antistatic bag if you do not have a mat available.
3. For the FB-DIMM you wish to remove, simultaneously pull both FB-DIMM
retainer clips outward from the slot (see
➊
in
FIGURE 2-2
).
4. Grasp the FB-DIMM by the edges, and carefully pull it out of its connector (see
➋
in
FIGURE 2-2
). A slight rocking motion might be required.
Caution –
Take extra care to prevent damage when removing the outer most
FB-DIMMs.
5. Place it in an antistatic bag.
Summary of Contents for Sun Netra CP3260
Page 18: ...xviii Sun Netra CP3260 Blade Server User s Guide April 2009...
Page 23: ...Chapter 1 Introduction 1 5 FIGURE 1 2 Netra CP3260 Blade Server Top View...
Page 24: ...1 6 Netra CP3260 Blade Server User s Guide April 2009...
Page 27: ...Chapter 1 Introduction 1 9 FIGURE 1 3 Netra CP3260 Blade Server in an ATCA Shelf Enclosure...
Page 36: ...1 18 Netra CP3260 Blade Server User s Guide April 2009...
Page 42: ...2 6 Netra CP3260 Blade Server User s Guide April 2009 FIGURE 2 1 FB DIMM Memory Locations...
Page 43: ...Chapter 2 Hardware Installation 2 7...
Page 44: ...2 8 Netra CP3260 Blade Server User s Guide April 2009...
Page 52: ...2 16 Netra CP3260 Blade Server User s Guide April 2009 FIGURE 2 5 TOD Battery Location...
Page 53: ...Chapter 2 Hardware Installation 2 17...
Page 61: ...Chapter 2 Hardware Installation 2 25 FIGURE 2 9 Hot Swap Latch and Hot Swap LED...
Page 62: ...2 26 Netra CP3260 Blade Server User s Guide April 2009...
Page 106: ...5 6 Netra CP3260 Blade Server User s Guide April 2009...
Page 140: ...B 8 Netra CP3260 Blade Server User s Guide April 2009...