3 | General safety instructions
05/2019 | ID 442790.01
17
3.6
Working on the machine
Before all work on machines and systems, apply the 5 safety rules in accordance with DIN VDE 0105-100 (Operation of
electrical installations – Part 100: General requirements) in the order listed:
§
Disconnect (also ensure that the auxiliary circuits are disconnected).
§
Ensure power cannot be switched on again.
§
Ensure that everything is de-energized.
§
Ground and short circuit.
§
Cover adjacent live parts.
Information
Note that the you can only determine that voltage is no longer present once the
of the drive controller. You can find the discharge time in the general technical data of
the drive controller.
3.7
Decommissioning
In safety-oriented applications, note the length of use T
M
= 20 years in the safety-relevant key performance indicators.
3.8
Disposal
Observe the current national and regional regulations when disposing of the product! Dispose of the individual product
parts depending on their properties, e.g. as:
§
Electronic waste (circuit boards)
§
Plastic
§
Sheet metal
§
Copper
§
Aluminum
§
Battery
3.9
Firefighting
DANGER!
Electrical voltage! Risk of fatal injury due to electric shock!
There is a risk of fatal injury due to electric shock when using conductive firefighting equipment.
▪
Use ABC powder or carbon dioxide (CO
2
) for firefighting.